Drolet ECO-35 owner manual Venting through wall, Venting trough wall, Equivalent Vent Lenght Evl

Models: ECO-35

1 30
Download 30 pages 54.73 Kb
Page 8
Image 8
EQUIVALENT VENT LENGHT (EVL)

EQUIVALENT VENT LENGHT (EVL)

The longer the run of pipe in your installation, the greater the restriction in the system. Therefore, larger diameter pipe should be used.

Use 4” pipe if you have more than 15 feet of Equivalent Vent Length (EVL).

Horizontal runs shall not exceed 10 feet of EVL.

To calculate EVL, use the following conversions table:

Qty

Type of pipe

EVL equivalent(ft)

1

90° elbow or “T”

5

1

45° elbow

3

1 ft

Horizontal pipe run

1

1 ft

Vertical pipe run

0.5

FOLLOW CHIMNEY OR VENT MANUFACTURER'S INSTRUCTIONS

WALL

THIMBLE

90 DEGREE ELBOW

45 DEGREE ELBOW

TERMINATION

COLLAR

WALL

STRAP

CLEAN OUT

TEE

NOTE: At altitudes above 3,000 feet, we suggest the use of 4” diameter vent at an EVL of 7 feet or more.

Figure 7

Venting through wall

Here is an example on how to calculate the EVL of your installation. (See Figure 8)

(3 x 4’ of vertical length = 12’ x 0.5 = 6 EVL) + (1 x elbow or "T" = 5 EVL) + (2 x 1’ of horizontal length = 2 EVL)

Total EVL = (6 + 5 +2) = 13. So 3” diameter vent is acceptable.

INSTALLATION CONFIGURATIONS

HORIZONTALLY THROUGH WALL

(refer to Figure 7 & 8)

NOTE: Follow Vent chimney manufacturer’s instructions.

1.

Position stove, adhering to clearances shown in Figures 1 & 2.

2.

Locate position of hole in wall; directly behind stove exhaust vent

 

(refer to figure 4).

FOLLOW CHIMNEY OR

VENT MANUFACTURER'S

INSTRUCTIONS

WALL

THIMBLE

VERTICAL ROOF VENT

VERTICAL LENGTH 4' EVL = 4 X 0.5' = 2'

VERTICAL LENGTH 4' EVL = 4 X 0.5' = 2'

WALL

STRAP

VERTICAL LENGTH4' EVL = 4 X 0.5' = 2'

CLEAN OUT

TEE

90° ELBOW "T" LEE = 5'

3.

Always maintain 3” clearance from combustible materials.

4.

Install Vent wall thimble per Vent manufacturer’s instructions.

5.

Attach enough piping to penetrate and extend at least 6” beyond

 

exterior walls. An 8-foot vertical pipe run is suggested where possible

 

to reduce the possibility of smoke spillage in the event of a loss of

 

negative pressure.

6.

Attach cap and seal outside wall thimbles with non-hardening

 

waterproof mastic.

Termination should not be located so that hot exhaust gases can ignite trees, shrubs, or grasses or be a hazard to children. Exhaust gases can reach temperatures of 500ºF and cause serious burns if touched.

1' HORIZONTAL RUN EVL = 1'

 

1' HORIZONTAL RUN EVL = 1'

 

 

 

Figure 8

Venting trough wall

Locate terminations: a) not less than 3 feet above any forced air inlet located within 10 feet; b) not less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air inlet into any building;

c)not less than two feet from an adjacent building and not less than 7 feet above grade when located adjacent to a public walkway. Mobile home installations must use a spark arrester. Other restrictions may apply, such as the need to maintain a minimum distance to a gas meter. US and Canadian Standards may vary. Consult the vent manufacturer’s instructions.

8

Page 8
Image 8
Drolet ECO-35 Venting through wall, Venting trough wall, Equivalent Vent Lenght Evl, Installation Configurations