Eaton Electrical BladeUPS Bar manual Wireway Terminal Block Housing Installation

Models: BladeUPS Bar

1 28
Download 28 pages 2.56 Kb
Page 17
Image 17
Figure 8. Wireway Terminal Block Housing Installation

INSTALLATION

17.Using two M6×12 hex bolts, secure the left side of the wireway terminal block housing to the rack. See Figure 8. Torque the bolts to 5.1 ± 0.8 Nm (45 ± 7 lb in).

18.Using nine M4×8 pan-head screws, secure the wireway terminal block housing to the wireway and to the bar. See Figure 8. Torque the screws to 1.7 ± 0.2 Nm (15 ± 2 lb in).

Wireway

Terminal Block

Housing

M6×12 Hex Bolts (2 places)

M4×8 Pan-Head Screws (9 places)

Figure 8. Wireway Terminal Block Housing Installation

EATON Powerware® BladeUPS® Bar Installation Guide S 164201723 Rev P01

13