Quick Installation Guide

Smart Wireless THUM Adapter

00825-0100-4075, Rev BA February 2010

© 2010 Rosemount Inc. All rights reserved. All marks property of owner.

Emerson Process Management

Rosemount Temperature GmbH

Emerson Process Management

Rosemount Division

Frankenstrasse 21

Asia Pacific Private Limited

8200 Market Boulevard

63791 Karlstein

1 Pandan Crescent

Chanhassen, MN USA 55317

Germany

 

Singapore 128461

T (US) (800) 999-9307

T 49 (6188)

992 0

T (65)

6777 8211

T (Intnl) (952) 906-8888

F 49 (6188)

992 112

F (65)

6777 0947 / (65) 6777 0743

F (952) 949-7001

 

 

Enquiries@AP.EmersonProcess.com

IMPORTANT NOTICE

This installation guide provides basic guidelines for the Smart Wireless THUM Adapter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations. Refer to the THUM Adapter Reference Manual (document number 00809-0100-4075) for more instruction. The manual and this QIG are also available electronically on www.rosemount.com.

WARNING

Explosions could result in death or serious injury:

Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the Product Certifications section for any restrictions associated with a safe installation.

Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.

Electrical shock can result in death or serious injury:

Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.

This device must be installed to ensure a minimum antenna separation distance of 7.87-in. (20 cm) from all persons.

IMPORTANT NOTICE

During normal operation, or in fault condition, the THUM Adapter will cause a 2.5 V drop in the connected loop. It is important to ensure that the power supply can provide at least

2.5V more than the minimum operating voltage of the wired device to make sure it works properly with the THUM Adapter installed. To determine the minimum operating voltage for the wired device, review the wired device operation and installation manual.