Quick Installation Guide

Smart Wireless THUM Adapter

00825-0100-4075, Rev BA February 2010

Remote Mount

Remote Mount: The THUM Adapter is mounted separate from the wired device housing and then connected to the wired device using conduit or other suitable means.

Figure 5. Remote Mount

1.Install the HART device according to standard installation practices and the manufacturer’s instructions, being sure to use an approved thread sealant on all connections.

2.The THUM Adapter should be mounted as shown in Figure 5 on page 6.

3.Ground the Remote Mount Kit per local practices.

4.Connect the THUM Adapter to the wired device using standard practices. Wire running from the THUM Adapter to the wired device should be shielded or in conduit when installed in electrically noisy environments.

5.Connect the THUM Adapter to the HART wired device using the wiring diagrams below. See Figure 21, 8, 10, and 12 on the following pages.

6.Close the housing cover on the HART wired device, so that metal touches metal, but do not over tighten to prevent damaging the unit.

NOTE

Two splice connectors are included with the THUM Adapter. The first is a two connection splice. The second is a three connection splice for use with a resistor, if there is not enough resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device reference manual for information on the required loop resistance.

6

Page 6
Image 6
Emerson 00825-0100-4075 manual Remote Mount