Emerson 00825-0100-4075 manual IECEx Certifications, Smart Wireless THUM Adapter, Loop Power

Models: 00825-0100-4075

1 28
Download 28 pages 44.97 Kb
Page 23
Image 23
IECEx Certifications

Quick Installation Guide

00825-0100-4075, Rev BA February 2010

Smart Wireless THUM Adapter

IECEx Certifications

I7 IECEx Intrinsic Safety

Certificate No.: IECEx BAS 09.0050X

Ex ia IIC T4 (-50 °C Tamb 70°C)

IP66

Table 3. Input Parameters

Loop Power

Ui = 30V

Ii = 200 mA

Pi = 1.0 W

Ci = 0

Li = 0

Special conditions for safe use (X)

The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.

The enclosure is made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0.

N7 IECEx Type n

Certificate No.: IECEx BAS 09.0058

Ex nA IIC T4 (-50 °C Tamb 70°C)

Ui = 45 Vdc MAX

IP66

23

Page 23
Image 23
Emerson 00825-0100-4075 manual IECEx Certifications, Smart Wireless THUM Adapter, Quick Installation Guide, Loop Power