Quick Installation Guide
Smart Wireless THUM Adapter
Hazardous Locations Certificates
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsically Safe and
Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G. Zone Marking: Class I, Zone 0, AEx ia llC
Temperature Codes T4
Intrinsically safe and
Enclosure Type 4X/IP66
CSA - Canadian Standards Association
I6 CSA Intrinsically Safe
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. T3C
Intrinsically safe when installed according to Rosemount Drawing
Enclosure Type 4X/IP66
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: Baseefa09ATEX0125X II 1G Ex ia IIC T4
IP66
1180
Table 2. Input Parameters
Loop Power
Ui = 30V
Ii = 200 mA
Pi = 1.0 W
Ci = 0
Li = 0
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic charge
The enclosure is made of aluminium alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in a zone 0.
N1 ATEX Type n |
|
Certificate No.: Baseefa09ATEX0131 | II 3 G |
Ex nA IIC T4 |
|
Ui = 45 Vdc MAX |
|
IP66 |
|
1180 |
|
22