STEP 2: VERIFY OPERATION

Quick Installation Guide

00825-0100-4075, Rev BA February 2010

Smart Wireless THUM Adapter

STEP 2: VERIFY OPERATION

Operation can be verified in three locations: by using the Field Communicator, at the Gateway via the Smart Wireless Gateway’s integrated web server, or via AMSWireless Configurator.

Field Communicator

For HART Wireless transmitter communication, a THUM Adapter DD is required.The Field Communicator must be put into poll mode using the THUM Adapter address of 63. Use the wired device documentation to connect the Field Communicator to the THUM Adapter.

Figure 24. Field Communicator Connections

 

Function

Key Sequence

Menu Items

Communications

3, 3

Join Status, Wireless Mode, Join Mode,

 

 

Number of Available Neighbors, Number of

 

 

Advertisements Heard, Number of Join

 

 

Attempts

Smart Wireless Gateway

If the THUM Adapter was configured with the Network ID and Join Key, and sufficient time has passed for network polling, the transmitter will be connected to the network. To verify device operation and connection to the network with the Smart Wireless Gateway’s integrated web server, open the Smart Wireless Gateway’s integral web interface and navigate to the Explorer page.

NOTE:

It may take several minutes for the device to join the network.

AMS Wireless Configurator

When the device has joined the network, it will appear in the Wireless Configurator as illustrated below.