ADJUSTMENTS (continued)
NOTICE
Do not make any setting changes while the controller is energized.
How to Change a Setting
1. Prevent the transfer switching device from operat- |
ing by disconnecting one source first, then the |
other, as follows: |
a. If the transfer switching device is in the Normal |
position, open the emergency source circuit |
breaker. Turn the engine starting control to off. |
Then open the normal source circuit breaker. |
b. If the transfer switching device is in the |
Emergency position, open the normal source |
circuit breaker. Turn engine starting control to |
cover | thumb |
| latch |
hook on left side
Figure 4-1. Controller cover latch.
| test or run. Then open the emergency source |
| circuit breaker. |
2. | Disconnect both harness plugs from controller by |
| squeezing the latches. Do not pull on the wires. |
3. | Remove cover from the controller by releasing latch |
| on right side with your thumb. See Figure |
4. | Locate the appropriate adjustment potentiometer or |
| DIP switch for the setting that you want to change. |
| Refer to Table |
| Figure |
5. | Use a small screwdriver to turn the potentiometer |
| clockwise to increase the time delay or counter- |
| clockwise to decrease it. See Figure |
harness plugs
S3 DIP switch
S1 DIP switch
S2 DIP switch
9 volt alkaline battery
J5 battery on/off jumper
P1 retransfer to normal time delay
P2 transfer to emergency time delay
6. | Use a | ||
| slide the switch actuators left or right so they match | ||
| the illustration next to the setting (left = off, right = | ||
| on). Recheck the setting. See Figure | ||
7. | Install the cover on the controller by hooking it on | ||
| the left side and latching the right side. | ||
8. | Reconnect both harness plugs to the controller by | ||
| aligning and pressing straight in until latches click. | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Close the automatic transfer switching equipment enclosure door and tighten the screws before restoring power.
9.Close the enclosure door, then restore both sources:
a.If the transfer switching device is in the Normal position first close the normal source circuit breaker, then close the emergency source cir- cuit breaker.
b.If the transfer switching device is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.
10. Turn the engine starting control to automatic.
Figure 4-2. Location of potentiometers, DIP switches, battery, and battery jumper.
clockwise to increase
P1 or P2 potentiometer
counterclockwise to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1
SW2