CONTROL FEATURES (continued)
5--2
OPTIONAL PROGRAMMABLE ENGINE EXERCISER (Ac cessory 11CD)
The optional programmableengine exerciser provides
seven days of different exercise periods. The timer is
connected and mounted below the controller. A
permanent backup battery maintains the setting;when
poweris lost to timer, output switch deenergizes.
DIP Switch Settings
FUNCTION S1 DIP
SWITCH
S2 DIP
SWITCH
Opt.Timer
Enabled
Actuator
7off
7
Actuator
5off
5
Opt.Timer
Disabled
Actuator
7off
7
Actuator
5on
5
Exercise
without
Load
Actuator
8off
8
Exercise
with
Load
Actuator
8on
8
ShadedDIP switches are standard factory settings.
The Accessory 11CD Programmable Engine Exerciser
incorporatesa 7 day time base, and therefore, each day of
theweek can be uniquely programmed to testthe engine
generator set either with or without load. The proper
controllersettings must be made to determine whether or
nott he test willbe conducted with or without load (refer
topage5–1forproperselection).Forconvenience,Block
Programmingis also provided,wherebyuptosevendays
canbe grouped together if the ON and OFF times are the
same.
Seenext page for instructions on setting the timer.