TESTING & SERVICE (continued)

MANUAL LOAD TRANSFER

This procedure will manually transfer the load if the controller is disconnected.

Do not manually operate the transfer switching device until both power sources are disconnected: open both circuit breakers.

1.Open normal and emergency source circuit breakers.

2.Use the maintenance handle to manually operate transfer switching device to the opposite source. See page 1–4, Manual Operation Test.

3.If the transfer switching device is in the Emergency position manually start the engine generator and then close the emergency source circuit breaker.

TROUBLE-SHOOTING

Note the control features that are activated or furnished on the switch and review their operation. Refer to Section 5, Control Features.

Proceed with care! The automatic transfer switching equipment is energized.

Table 3-1. Trouble-Shooting Checks.

PROBLEM

CHECK IN NUMERICAL SEQUENCE

1 OPERATION

2 GEN-SET

3 VOLTAGE

 

Gen-Set does not start when

Hold the TRANSFER SWITCH

Starting control must be in

 

the TRANSFER SWITCH TEST

TEST button 15 sec. or the

automatic position. Batteries

 

button is pressed and held for

outage must be long enough

must be charged and

 

15 seconds or when the

to allow for the 1 or 3 sec.

connected. Check wiring to

normal source fails.

Momentary Normal Source

engine starting contacts.

 

 

Outage Delay plus engine

 

 

 

cranking and starting time.

 

 

 

 

 

 

Transfer switching device

Wait for Transfer to Emergen-

Generator output circuit

Voltmeter should read at least

does not transfer the load to

cy Delay (0 to 5 min.) to time

breaker must be closed.

90% of nominal phase to

emergency source after the

out. For immediate transfer,

Generator frequency must be

phase voltage between

gen-set starts.

press the BYPASS TIME

at least 95% of nominal

transfer switch terminals U2

 

DELAY button. If Motor Load

(48 Hz for a 50 Hz system).

and W2 (or L1 and L5 for 2

 

Transfer is active, wait for in-

 

pole switches). *

 

phase condition (see below).

 

* These are factory settings.

 

 

 

 

Transfer switching device

Wait for Retransfer to Normal

 

Voltmeter should read at least

does not transfer the load to

Delay (1 sec. to 30 min.) to

 

90% of nominal phase to

normal source when normal

time out. For immediate re–

 

phase voltage between

returns or when TRANSFER

transfer, press BYPASS TIME

transfer switching device

SWITCH TEST button is

DELAY button. If Motor Load

 

terminals V1 and W1, W1 and

released.

Transfer is active, wait for in-

 

U1, and U1 and V1 (or L2 and

 

phase condition (see below).

 

L6 for 2 pole switches).

 

 

 

 

Gen-Set does not stop after

Wait for the 5 minute

Starting control must be in

 

load retransfer to the normal

Unloaded Running Delay to

automatic position.

source.

time out.

 

 

 

 

 

 

Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)

Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !

1.Connect a voltmeter (set for twice system phase–to–phase voltage) between transfer switching device terminals U1 and U2 (for 3 pole) or L1 and L2 (for 2 pole).

2.Manually start generator. Voltmeter needle should sweep back and forth at a regular rate between 0 and about twice system voltage.

3.Press and hold the Transfer Test button. The load should transfer to emergency source when meter needle is near 0 volts. If transfer does not occur, Motor Load Transfer feature is not operating.

4.Release the Transfer Test button. The load should retransfer back to the normal source after the Retransfer to Normal Delay, if used. The retransfer should occur when the needle is near 0 volts. If retransfer does not occur after the time delay, the Motor Load Transfer feature is not operating.

5.For immediate retransfer, press the Bypass Time Delay button. Then disconnect the voltmeter.

If the problem is isolated to circuits on the controller or the transfer switching device, call your local ASCO Power Technologies sales office. Furnish Serial No., Bill of Material (BOM) No., & Catalog No. from the transfer switching device nameplate.

3--2

Page 10
Image 10
Emerson 381333234 E manual Testing & Service, Manual Load Transfer, Trouble-Shooting, Check in Numerical Sequence