Retransfer to Normal
When the normal source is accepted by the sensor, relay SE begins its timing cycle (adjustable 1 sec. to 30 min., retransfer to normal delay). For immediate retransfer press Bypass Time Delay button. SE relay is provided with a time delay on pickup to prevent immediate load retransfer to the normal source. The delay insures that the normal source has stabilized before reconnection of vital loads. If the normal source voltage falls below the present dropout point before the time delay expires, the timing cycle is reset to zero. If the emergency source fails for more than 4 seconds during the timing cycle, ER relay drops out and the load is immediately retransferred to the normal source, if that source is acceptable.
SE relay energizes and ER relay is dropped out. The TS coil is energized, the transfer switching device oper- ates, and all switch contacts (mains, controls, auxilia- ries) reverse position. The transfer switching device is now supplying the load from the normal source again.
Upon retransfer to the normal source, NR relay begins its timing cycle (unloaded running delay [engine cool- down] ). NR relay is provided with a 5 minute time delay on pickup to keep the engine running for a cool-down period.
NR relay energizes after the time delay and signals the engine-driven generator to shut down. All circuits are reset for any future normal source failure.
Activation of standard control features shown in Section 5 will alter the sequence of operation and introduce additional time delays during transfer operations.
The sequence for load retransfer to the normal source automatically begins when the voltage sensor detects restoration of the normal source. The voltage level must rise above the preset pickup point on all phases before the sensor will accept the normal source.
Figure 2–1. Membrane controls and indicator lights.

SECTION 2 SEQUENCE OF OPERATION

Lights show position of transfer switching device.

Lights show the sources accepted.

Transfer To Emergency

The sequence for load transfer to emergency source begins automatically when normal source voltage falls below the preset dropout point or when Transfer Test button is pressed. An under voltage condition on any phase of the normal source is detected by the sensor.

When

the

normal

 

 

 

source

voltage fails

 

 

 

or the Transfer Test

Hold 15 sec. to

Press to cancel the

Hold 5 sec. to set

button is pressed, the

start the engine

active exercise period

20 min. engine exercise

SE relay de-ener-

generator and to

(stops engine now or

period immediately (engine

gizes and relay NR

transfer the load

after cooldown) See

starts) and weekly thereafter.

begins

its

timing

to emergency.

page 5–1.

 

cycle (1 or 3 seconds,

 

 

 

momentary

normal

 

 

 

source outage delay). The NR relay is provided with a time

 

delay on dropout to override momentary outages and

 

prevent nuisance starting of the engine-driven generator. If the normal source voltage returns above the sensor dropout setting before the time delay expires, the NR relay timing cycle is reset to zero and relay SE energizes.

If the normal source voltage does not return above the sensor dropout setting before the time delay expires, the NR relay de-energizes and signals the engine-driven generator to start. At the same time, a voltage and frequency sensor begins monitoring the emergency source. The sensor will accept the emergency source only when both voltage and frequency reach preset pickup points. Usually about ten seconds elapse from dropout of the NR relay to acceptance by the sensor. This time span occurs because the engine-driven generator must crank, start, and run up to nominal pickup points. For this reason, if the Transfer Test button is pressed it must be held for 15 seconds. If the emergency source is available immediately, the sensor may accept it as soon as NR relay drops out.

When the emergency source is accepted by the sensor, relay ER begins its timing cycle (transfer to emergency delay). ER relay is provided with an adjustable (0 to 5 minutes) time delay on pickup to delay transfer of the load to the emergency source. For immediate transfer press Bypass Time Delay button.

ER relay energizes, the TS coil is energized, the transfer switching device operates, and all switch contacts (mains, controls, auxiliaries) reverse position. The transfer switch is now supplying the load from the emergency source.

The transfer switching device will remain in the Emergency position until the normal source is restored. If the Transfer Test button is used, the transfer switching device will remain on emergency until the retransfer to normal delay times out.

Light for built–in

engine exercise timer:

³blinks rapidly when button is held 5 sec.

while being set

³blinks slowly when button is released (set)

and during 20 min. exercise period.

³stays on after engine stops (exerciser is

enabled for weekly operation)

See page 5–1 for complete instructions

2---1

Page 8
Image 8
Emerson 381333234 E manual Sequence of Operation, Transfer To Emergency