Emerson 610 installation manual Site planning data-600V input

Models: 610

1 112
Download 112 pages 63.15 Kb
Page 106
Image 106

100

Table 6

 

Site planning data—600V input

 

 

 

 

 

 

 

 

 

UPS

 

 

AC Output

Options

Rectifier AC

Inverter

Required

Max. Battery

Max. Heat

Dimensions

Approx. Weight

Floor Loading

Rating

 

Voltage

Input Current

Output Current

Unpacked

Concentrated Loading

 

 

 

 

 

 

 

 

 

 

 

 

Battery

Current

Dissipation

 

 

 

kVA

 

kW

 

VAC

Input

Input

Nom

 

Max

Nom

Max

Disconnect

at End of

Full Load

WxDxH:

lb. (kg)

lb./ft.2 (kg/m2)

 

 

Filter

Xformer

 

Rating (A)

Discharge (A)

BTU/h (kWH)

in. (mm)

500

 

400

 

600

NO

NO

484

 

605

481

601

1000

1079

94,900 (27.8)

72x39x78

6110 (2771)

313 (1528)

500

 

400

 

600

YES

NO

449

 

561

481

601

1000

1079

99,600 (29.2)

(1829x991x1981)

6310 (2862)

324 (1582)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

 

600

NO

YES

490

 

612

481

601

1000

1079

118,700 (34.8)

96x39x78

8710 (3951)

335 (1636)

500

 

400

 

600

YES

YES

454

 

567

481

601

1000

1079

123,570 (36.2)

(2438x991x1981)

8910 (4042)

343 (1675)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

 

600

NO

NO

545

 

681

481

601

1200

1214

106,750 (31.3)

72x39x78

6130 (2781)

314 (1533)

500

 

450

 

600

YES

NO

505

 

631

481

601

1200

1214

112,050 (32.8)

(1829x991x1981)

6330 (2871)

325 (1587)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

 

600

NO

YES

551

 

688

481

601

1200

1214

133,550 (39.1)

96x39x78

9030 (4096)

347 (1694)

500

 

450

 

600

YES

YES

510

 

638

481

601

1200

1214

139,010 (40.7)

(2438x991x1981)

9230 (4187)

355 (1733)

 

 

 

 

625

 

500

 

600

NO

NO

602

 

753

601

752

1400

1349

108,950 (31.9)

108x39x78

7805 (3540)

300 (1465)

625

 

500

 

600

YES

NO

559

 

699

601

752

1400

1349

118,650 (34.7)

(2743x991x1981)

8025 (3640)

309 (1509)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

500

 

600

NO

YES

609

 

761

601

752

1400

1349

128,450 (37.6)

120x39x78

10485 (4756)

323 (1577)

625

 

500

 

600

YES

YES

564

 

705

601

752

1400

1349

134,400 (39.4)

(3048x991x1981)

10705 (4856)

329 (1606)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

600

NO

NO

723

 

903

722

902

1600

1619

130,700 (38.3)

108x39x78

8405 (3812)

323 (1577)

750

 

600

 

600

YES

NO

671

 

839

722

902

1600

1619

142,350 (41.7)

(2743x991x1981)

8625 (3912)

332 (1621)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

600

NO

YES

730

 

913

722

902

1600

1619

154,150 (45.1)

 

11485 (5210)

353 (1723)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

600

YES

YES

677

 

846

722

902

1600

1619

161,250 (47.2)

120x39x78

11705 (5309)

360 (1758)

750

 

675

 

600

NO

YES

822

 

945

722

902

1600

1822

173,400 (50.8)

(3048x991x1981)

11785 (5346)

363 (1772)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

675

 

600

YES

YES

762

 

876

722

902

1600

1822

181,400 (53.1)

 

12005 (5445)

369 (1802)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Notes (p. 99):

13

1,4,5,7,8,9,11,12

2,3,5,7,8,9,11,12

6

6,8,9,11,12

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Site Planning Data, Series 610, 500-750kVA, Multi-Module Systems