Configuring Your Neutral and Ground Connections

6.6Preferred Grounding Configuration, Battery Systems

Open-rack battery systems, depending on local code requirements and customer preference, are normally:

1.Floating (ungrounded),

2.Center-tapped and floating or

3.Center tapped and grounded.

Battery cabinet systems must be connected as floating (ungrounded) systems—Option 1 above. Center-tapped or grounded battery systems are not possible with battery cabinet systems.

Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus.

Figure 10 illustrates how a simple, one-cabinet system would be grounded. For systems with multi- ple cabinets, the same configuration would apply. However, for simplicity, the installer can connect all the battery cabinet grounds for a particular module together and run a single ground conductor to that UPS module ground (in the same conduit as the phase conductors).

Figure 10 Preferred grounding configuration, battery systems

20

Page 26
Image 26
Emerson 610 Preferred Grounding Configuration, Battery Systems, Preferred grounding configuration, battery systems