101

Table 7

 

Site planning data—480V input

 

 

 

 

 

 

 

 

 

UPS

 

 

AC Output

Options

Rectifier AC

Inverter

Required

Max. Battery

Max. Heat

Dimensions

Approx. Weight

Floor Loading

Rating

 

Voltage

Input Current

Output Current

Unpacked

Concentrated Loading

 

 

 

 

 

 

 

 

 

 

 

 

Battery

Current

Dissipation

 

 

 

kVA

 

kW

 

VAC

Input

Input

Nom

 

Max

Nom

Max

Disconnect

at End of

Full Load

WxDxH:

lb. (kg)

lb./ft.2 (kg/m2)

 

 

Filter

Xformer

 

Rating (A)

Discharge (A)

BTU/h (kWH)

in. (mm)

500

 

400

 

480

NO

NO

602

 

753

601

752

1000

1079

87,150 (25.5)

72x39x78

5710 (2590)

293 (1431)

500

 

400

 

480

YES

NO

558

 

698

601

752

1000

1079

91,790 (26.9)

(1829x991x1981)

5910 (2681)

303 (1479)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

400

 

480

NO

YES

612

 

765

601

752

1000

1079

110,700 (32.4)

96x39x78

8710 (3951)

335 (1636)

500

 

400

 

480

YES

YES

567

 

709

601

752

1000

1079

115,550 (33.8)

(2438x991x1981)

8910 (4042)

343 (1675)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

 

480

NO

NO

677

 

847

601

752

1200

1214

98,050 (28.7)

72x39x78

5730 (2599)

294 (1435)

500

 

450

 

480

YES

NO

628

 

785

601

752

1200

1214

103,250 (30.2)

(1829x991x1981)

5930 (2690)

304 (1484)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

 

480

NO

YES

688

 

861

601

752

1200

1214

124,550 (36.5)

96x39x78

9030 (4096)

347 (1694)

500

 

450

 

480

YES

YES

638

 

798

601

752

1200

1214

129,950 (38.1)

(2438x991x1981)

9230 (4187)

355 (1733)

 

 

 

 

625

 

500

 

480

NO

NO

749

 

936

752

940

1400

1349

99,300 (29.1)

108x39x78

7405 (3359)

285 (1391)

625

 

500

 

480

YES

NO

694

 

867

752

940

1400

1349

105,050 (30.8)

(2743x991x1981)

7625 (3459)

293 (1431)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

500

 

480

NO

YES

757

 

946

752

940

1400

1349

118,650 (34.7)

120x39x78

10485 (4756)

323 (1577)

625

 

500

 

480

YES

YES

701

 

877

752

940

1400

1349

124,500 (36.5)

(3048x991x1981)

10705 (4856)

329 (1606)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

480

NO

NO

898

 

1123

902

1128

1600

1619

119,200 (34.9)

108x39x78

8005 (3631)

308 (1504)

750

 

600

 

480

YES

NO

833

 

1041

902

1128

1600

1619

126,100 (36.9)

(2743x991x1981)

8225 (3731)

316 (1543)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

480

NO

YES

908

 

1135

902

1128

1600

1619

142,350 (41.7)

 

11485 (5210)

353 (1723)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

600

 

480

YES

YES

842

 

1052

902

1128

1600

1619

149,400 (43.7)

120x39x78

11705 (5309)

360 (1758)

750

 

675

 

480

NO

YES

1022

 

1175

902

1128

1600

1822

160,150 (46.9)

(3048x991x1981)

11785 (5346)

363 (1772)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

 

675

 

480

YES

YES

947

 

1089

902

1128

1600

1822

168,100 (49.2)

 

12005 (5445)

369 (1802)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Notes (p. 99):

13

1,4,5,7,8,9,11,12

2,3,5,7,8,9,11,12

6

6,8,9,11,12

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Site Planning Data, Series 610, 500-750kVA, Multi-Module Systems

Page 107
Image 107
Emerson 610 installation manual Site planning data-480V input