Emerson 610 installation manual Preferred Grounding Configuration With Isolated Bypass

Models: 610

1 112
Download 112 pages 63.15 Kb
Page 22
Image 22

Configuring Your Neutral and Ground Connections

6.3Preferred Grounding Configuration With Isolated Bypass

Another configuration in this power range is the Multi-Module System with 480 or 600 VAC input, 208 VAC output, a Bypass Isolation Transformer and a connected load consisting of multiple distribu- tion panelboards or switchboards. Figure 6 shows a typical installation.

The Bypass Transformer provides isolation and may step down the voltage to the bypass input. The Bypass Transformer and the SCC together constitute a separately derived system, since there is no direct electrical connection between the input (service entrance) circuit conductors and the output cir- cuit conductors.

NOTE

Figure 6 shows a wye-connected source, but the same grounding scheme would apply for a delta source at the service entrance.

The bonding of the neutral to the grounding conductor can theoretically be done at either the SCC or the Bypass Transformer. However, we recommend bonding at the Bypass Transformer because the UPS module will sometimes be powered down for maintenance and its output transformer will be out of the circuit. The neutral should be bonded to ground and a local grounding electrode should be installed at the Bypass Transformer, per NEC 250-30.

Figure 6 Preferred grounding configuration with isolated bypass

Features of this configuration include:

The UPS receives its bypass neutral from the Bypass Transformer

The output is isolated from the input circuit conductors, and

Some amount of common-mode noise attenuation can be obtained for sensitive loads if the UPS module and Bypass Transformer are located close to sensitive loads.

16

Page 22
Image 22
Emerson 610 Preferred Grounding Configuration With Isolated Bypass, Preferred grounding configuration with isolated bypass