Wiring Inspection

9.0WIRING INSPECTION

1.Verify all power connections are tightened per the torque specifications in Table 3.

2.Verify all control wire terminations are tight.

3.Verify all power wires and connections have proper spacing between exposed surfaces, phase-to- phase and phase-to-ground.

4.Verify that all control wires are run in steel conduit, separate from all power wiring.

Table 2

Power wiring terminals, factory supplied

 

 

UPS Module Rating

Connection Type

 

 

 

 

500kVA,

All power connections are top or bottom cable entry to busbars on the right side of

6-Pulse Rectifier

module.

 

500kVA,

Busbars for DC input, AC output, Neutral and Ground are provided on the right side of

12-Pulse Rectifier

module, with top or bottom cable entry. Rectifier input is top entry directly to lugs on top

 

 

of input circuit breaker.

625-750kVA,

Busbars for AC output, Neutral and Ground are provided on the right side of module,

standard models with

with top or bottom cable entry. Rectifier input is top entry directly to lugs on top of input

standard input

circuit breaker. DC input is top entry to busbars.

750kVA/675 kW

Busbars for AC output, Neutral and Ground are provided on the right side of module,

and other modules with

with top or bottom cable entry. Rectifier input and DC input are top entry to busbars.

optional input busbar kit

 

Use 75°C copper wire. Select wire size based on the ampacities in Table 5 of this manual, a reprint of Table 310-16 and associated notes of the National Electrical Code (NFPA 70).

Use commercially available solderless lugs for the wire size required for your application. Refer to Table 3. Connect wire to the lug using tools and procedures specified by the lug manufacturer.

Table 3

Torque specifications

 

 

 

 

 

 

 

 

 

NUT AND BOLT COMBINATIONS

 

 

 

 

 

 

 

 

Electrical Connections

 

 

Grade 2 Standard

with Belleville Washers

 

Bolt Shaft Size

Lb-in

N-m

Lb-in

N-m

 

1/4

53

6.0

46

5.2

 

5/16

107

12

60

6.8

 

3/8

192

22

95

11

 

1/2

428

22

256

29

 

 

 

 

 

CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)

 

 

 

Wire Size or Range

Lb-in

N-m

 

 

 

#6 - #4

100

11

 

 

 

#3 - #1

125

14

 

 

 

1/0 - 2/0

150

17

 

 

 

3/0 - 200 MCM

200

23

 

 

 

250 - 400 MCM

250

28

 

 

 

500 - 700 MCM

300

34

 

 

 

 

 

 

 

CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)

 

 

 

Current Rating

Lb-in

N-m

 

 

 

400 - 1200 Amps

300.00

34.00

 

 

 

 

 

 

 

TERMINAL BLOCK COMPRESSION LUGS (FOR CONTROL WIRING)

 

 

AWG Wire Size or Range

Lb-in

N-m

 

 

 

#22 -#14

3.5 to 5.3

0.4 to 0.6

 

 

NOTE: Use the values in this table unless the equipment is labeled with a different torque value.

28

Page 34
Image 34