Wiring Inspection
9.0WIRING INSPECTION
1.Verify all power connections are tightened per the torque specifications in Table 3.
2.Verify all control wire terminations are tight.
3.Verify all power wires and connections have proper spacing between exposed surfaces,
4.Verify that all control wires are run in steel conduit, separate from all power wiring.
Table 2 | Power wiring terminals, factory supplied | |
|
| |
UPS Module Rating | Connection Type | |
|
|
|
| 500kVA, | All power connections are top or bottom cable entry to busbars on the right side of |
module. | ||
| 500kVA, | Busbars for DC input, AC output, Neutral and Ground are provided on the right side of |
module, with top or bottom cable entry. Rectifier input is top entry directly to lugs on top | ||
|
| of input circuit breaker. |
Busbars for AC output, Neutral and Ground are provided on the right side of module, | ||
standard models with | with top or bottom cable entry. Rectifier input is top entry directly to lugs on top of input | |
standard input | circuit breaker. DC input is top entry to busbars. | |
750kVA/675 kW | Busbars for AC output, Neutral and Ground are provided on the right side of module, | |
and other modules with | with top or bottom cable entry. Rectifier input and DC input are top entry to busbars. | |
optional input busbar kit |
|
Use 75°C copper wire. Select wire size based on the ampacities in Table 5 of this manual, a reprint of Table
Use commercially available solderless lugs for the wire size required for your application. Refer to Table 3. Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Table 3 | Torque specifications |
|
|
|
|
|
|
|
|
| |
NUT AND BOLT COMBINATIONS |
|
|
|
| |
|
|
|
| Electrical Connections | |
|
| Grade 2 Standard | with Belleville Washers | ||
| Bolt Shaft Size | ||||
| 1/4 | 53 | 6.0 | 46 | 5.2 |
| 5/16 | 107 | 12 | 60 | 6.8 |
| 3/8 | 192 | 22 | 95 | 11 |
| 1/2 | 428 | 22 | 256 | 29 |
|
|
|
|
| |
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING) |
|
| |||
| Wire Size or Range |
|
| ||
| #6 - #4 | 100 | 11 |
|
|
| #3 - #1 | 125 | 14 |
|
|
| 1/0 - 2/0 | 150 | 17 |
|
|
| 3/0 - 200 MCM | 200 | 23 |
|
|
| 250 - 400 MCM | 250 | 28 |
|
|
| 500 - 700 MCM | 300 | 34 |
|
|
|
|
|
|
| |
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING) |
|
| |||
| Current Rating |
|
| ||
| 400 - 1200 Amps | 300.00 | 34.00 |
|
|
|
|
|
|
| |
TERMINAL BLOCK COMPRESSION LUGS (FOR CONTROL WIRING) |
|
| |||
AWG Wire Size or Range |
|
| |||
| #22 | 3.5 to 5.3 | 0.4 to 0.6 |
|
|
NOTE: Use the values in this table unless the equipment is labeled with a different torque value.