Battery Installation

5.4Open-Rack Batteries

When batteries other than Liebert battery cabinets are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Refer to Required Battery Discon- nect Rating in the site planning data tables in Appendix A for recommended overcurrent protection ratings. Contact your Liebert sales representative for more information.

1.Install battery racks/cabinets and batteries per manufacturer’s installation and maintenance instructions.

2.Verify battery area has adequate ventilation and battery operating temperature complies with manufacturer’s specification. Installations using vented lead-acid batteries MUST have adequate ventilation to remove explosive gases per local and national codes.

3.Low voltage control wiring must be kept separate from power wiring and run in separate conduits.

4.Ensure that battery racks are properly grounded according to code requirements in your area.

If you have any questions concerning batteries, battery racks or accessories, contact your local sales representative or Liebert Global Services at 1-800-LIEBERT.

! CAUTION

Cables between batteries and the UPS modules should be run in matched pairs, positive-with-negative, within each conduit or cable run. Grouping like-polarity cables together (i.e., positive-with-positive and negative-with-negative) can cause stress or damage to the cables, conduit or buswork.

12

Page 18
Image 18
Emerson 610 installation manual Open-Rack Batteries