Installation Considerations
1.0INSTALLATION CONSIDERATIONS
Install your Series 610 UPS in accordance with the submittal drawing package and the following pro- cedures.
A Liebert authorized representative must perform the initial system
! CAUTION
Read this manual thoroughly before attempting to wire or operate the unit. Improper installation is the most significant cause of UPS
Do not install this equipment near gas or electric heaters. It is preferable to install the UPS in a restricted location to prevent access by unauthorized personnel.
1.Proper planning will speed unloading, location and connection of the UPS. Refer to Figures 13 through 78 and Appendix A.
2.Be certain that the floor at the final equipment location and along the route (inside the facility) to the installation site can support the cabinet weight and the weight of any moving equipment. The modules weigh from 5710 to 12,005 lbs. (2590 to 5445kg). The battery cabinets weigh from 3060 to 5300 lbs. (1388 to 2404kg). The System Control Cabinets weigh from 1000 to 5850 lbs. (454 to 2653kg). Refer to Appendix A. For switchgear weights, refer to your submittal package.
! WARNING
Locate center of gravity symbols and determine unit weight before handling cabinet.
3.Plan the route to ensure that the unit can move through all aisleways and doorways and around corners without risking damage. If the modules and batteries must be moved by elevator, check the size of the door openings and the
4.Refer to information later in this manual regarding the optional battery cabinets and Transformer Cabinets. Observe all battery safety precautions when working on or near the battery.
5.Use the shortest output distribution cable runs possible, consistent with logical equipment arrangements and with allowances for future additions if planned.
6.Recommended ambient operating temperature is 77°F (25°C). Relative humidity must be less than 95%,
7.Even though your Liebert UPS unit is at least
8.The installer should attempt to balance the load between the three output phases. The UPS will operate safely with an unbalanced load, but will give optimum performance if the three output phases are loaded within 20 percent of each other.
9.During normal UPS operations,
NOTE
While Liebert can provide typical guidelines, the responsibility for the proper breaker trip settings outside of the