14. User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

 

Every 14

Every 7 days (168

Sets the interval at which the unit will

Automatic Self-Test

days (336

hours), On Startup

execute a self-test.

 

hours)

Only, No Self-Test

 

 

 

 

 

 

 

 

Up to eight characters

Use this field to uniquely identify the

Unit ID

UPS_IDEN

unit for network management

 

 

to define the unit.

purposes.

 

 

 

 

 

 

 

Date of Last Battery

Manufacture

Date of Battery

Reset this date on battery replacement.

Replacement

Date

Replacement

 

 

 

 

 

Minimum Capacity

 

 

The unit will charge its batteries to the

Before Return from

0 percent

15, 50, or 90 percent

specified percentage before return

Shutdown

 

 

from a shutdown.

 

 

 

 

 

 

 

Set lower than normal sensitivity to

Sensitivity

Normal

Reduced, Low

avoid lowered battery capacity and

service life in situations where the load

 

 

 

 

 

 

can tolerate minor power disturbances.

 

 

 

 

 

 

 

Sets the time before shutdown at

Duration of Low

 

 

which the unit issues a low battery

2 minutes

5, 7, or 10 minutes

warning. Set higher than the default

Battery Warning

 

 

only if the OS needs the time for

 

 

 

 

 

 

graceful shutdown.

 

 

 

 

Alarm Delay After

5 second

30 second delay, At

To avoid alarms for minor power

Low Battery

Line Fail

delay

glitches, set the alarm delay.

Condition, No Alarm

 

 

 

 

 

 

 

 

 

180, 300, or 600

Sets the interval between when the

Shutdown Delay

20 seconds

unit receives a shutdown command

seconds

 

 

and when shutdown occurs.

 

 

 

 

 

 

 

 

 

 

To avoid branch circuit overload, the

Synchronized Turn-on

0 seconds

60, 180, 300 seconds

unit will wait the specified time after

Delay

the return of utility power before

 

 

 

 

 

turn-on.

 

 

 

 

High Transfer Point

132 Vac

135, 138, 129 Vac

 

 

 

 

 

Low Transfer Point

103 Vac

100, 97, 106 Vac

 

 

 

 

 