14. User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory | User Selectable | Description | |
Default | Choices | |||
|
| |||
|
|
|
| |
| Every 14 | Every 7 days (168 | Sets the interval at which the unit will | |
Automatic | days (336 | hours), On Startup | ||
execute a | ||||
| hours) | Only, No | ||
|
| |||
|
|
|
| |
|
| Up to eight characters | Use this field to uniquely identify the | |
Unit ID | UPS_IDEN | unit for network management | ||
|
| to define the unit. | purposes. | |
|
|
| ||
|
|
|
| |
Date of Last Battery | Manufacture | Date of Battery | Reset this date on battery replacement. | |
Replacement | Date | Replacement | ||
| ||||
|
|
|
| |
Minimum Capacity |
|
| The unit will charge its batteries to the | |
Before Return from | 0 percent | 15, 50, or 90 percent | specified percentage before return | |
Shutdown |
|
| from a shutdown. | |
|
|
|
| |
|
|
| Set lower than normal sensitivity to | |
Sensitivity | Normal | Reduced, Low | avoid lowered battery capacity and | |
service life in situations where the load | ||||
|
|
| ||
|
|
| can tolerate minor power disturbances. | |
|
|
|
| |
|
|
| Sets the time before shutdown at | |
Duration of Low |
|
| which the unit issues a low battery | |
2 minutes | 5, 7, or 10 minutes | warning. Set higher than the default | ||
Battery Warning | ||||
|
| only if the OS needs the time for | ||
|
|
| ||
|
|
| graceful shutdown. | |
|
|
|
| |
Alarm Delay After | 5 second | 30 second delay, At | To avoid alarms for minor power | |
Low Battery | ||||
Line Fail | delay | glitches, set the alarm delay. | ||
Condition, No Alarm | ||||
|
|
| ||
|
|
|
| |
|
| 180, 300, or 600 | Sets the interval between when the | |
Shutdown Delay | 20 seconds | unit receives a shutdown command | ||
seconds | ||||
|
| and when shutdown occurs. | ||
|
|
| ||
|
|
|
| |
|
|
| To avoid branch circuit overload, the | |
Synchronized | 0 seconds | 60, 180, 300 seconds | unit will wait the specified time after | |
Delay | the return of utility power before | |||
|
| |||
|
|
| ||
|
|
|
| |
High Transfer Point | 132 Vac | 135, 138, 129 Vac |
| |
|
|
|
| |
Low Transfer Point | 103 Vac | 100, 97, 106 Vac |
| |
|
|
|
|
26