12. Specifications

 

450 VA

 

700 VA

 

1000 VA

1400 VA

 

2200 VA

 

3000 VA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Acceptable input voltage

 

 

 

 

0 - 160 VAC

 

 

 

 

English

 

 

 

 

 

 

 

 

 

 

 

 

Maximum input voltage range*

 

 

 

 

92-146 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output voltage*

 

 

 

 

103-132 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal input frequency

 

 

 

 

50 or 60 Hz, autosensing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Protection

 

 

 

 

Resettable circuit breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency limits (on-line operation)

 

 

 

 

50 or 60 Hz, ±5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer time

 

 

 

2 ms typical, 4 ms maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum load

450 VA

 

700 VA

 

1000 VA

1400 VA

 

2200 VA

 

3000 VA

 

280 W

 

450 W

 

670 W

950 W

 

1600 W

 

2250 W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On-battery output voltage

 

 

 

 

115 VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

On-battery frequency

50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during

 

 

 

 

 

brownout.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

On-battery waveshape

 

 

 

 

Low-distortion sine wave

 

 

 

 

 

 

 

 

 

 

 

Protection

Overcurrent and short-circuit protected, latching shutdown on

 

 

 

 

 

overload

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge energy rating

320 J

 

 

480 J

 

 

 

(one time, 10/1000 µs waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge current capability

 

 

 

 

6500 A maximum

 

 

 

 

 

(one time, 8/20 µs waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge response time

 

 

0 ns (instantaneous) normal mode;

 

 

 

 

 

 

 

<5 ns common mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Surge voltage let-through

 

 

 

 

 

 

 

 

 

 

 

 

(percentage of applied ANSI C62.41 Cat. A

0.70%

 

 

0.30%

 

 

 

 

±6 kV test waveform)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noise Filter

 

Normal and common mode EMI/RFI suppression,

 

 

 

 

 

100 kHz to 10 MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery type

 

 

Spill proof, maintenance free, sealed lead-acid

 

 

 

 

 

 

 

 

 

 

 

Typical battery life

3 to 6 years, depending on number of discharge cycles and

 

 

 

 

 

ambient temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Typical recharge time

 

 

2 to 5 hours from total discharge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Adjustable via optional software.