Reference Manual

00809-0400-4728, Rev AA June 2011

Rosemount 644

Table 3-1.

RB.RECOMMENDED_ACTION

Sensor Transducer Block

 

 

Failed/Maint/Advise

Recommended Action

 

Alarm Type

Active Event

Text String

 

None

None

No action required

 

 

NV Writes Deferred

Non-volatile writes have been deferred, leave

 

Advisory

 

the device powered until the advisory goes

 

 

 

away

 

 

Configuration Error

Re-write the Sensor Configuration

 

 

Primary Value

Confirm the operating range of the applied

 

 

Degraded

sensor and/or verify the sensor connection and

Alerts

Maintenance

 

device environment

 

Calibration Error

Retrim the device

 

Secondary Value

Verify the ambient temperature is within

PlantWeb

 

Degraded

operating limits

 

Electronics Failure

Replace the Device

 

HW / SW Incompatible

Verify the Hardware Revision is compatible with

 

 

the Software Revision

 

 

 

 

 

NV Memory Failure

Reset the device then download the Device

 

Failed

 

Configuration

 

Primary Value Failure

Verify the instrument process is within the

 

 

 

 

 

Sensor range and / or confirm sensor

 

 

 

configuration and wiring.

 

 

Secondary Value

Verify the ambient temperature is within

 

 

Failure

operating limits

NOTE

When the engineering units of the XD_SCALE are selected, the engineering units in the Transducer Block change to the same units. THIS IS THE ONLY WAY TO CHANGE THE ENGINEERING UNITS IN THE SENSOR TRANSDUCER BLOCK.

Damping

Analog Input (AI) Function Block

The damping parameter in the Transducer Block may be used to filter measurement noise. By increasing the damping time, the transmitter will have a slower response time, but will decrease the amount of process noise that is translated to the Transducer Block Primary Value. Because both the LCD and AI Block get input from the Transducer Block, adjusting the damping parameter will effect both blocks.

NOTE

The AI Block has it's own filtering parameter called PV_FTIME. For simplicity, it is better to do filtering in the Transducer Block as damping will be applied to primary value on every sensor update. If filtering is done in AI block, damping will be applied to output every macrocycle. The LCD will display value from Transducer block.

Configure the AI block

A minimum of four parameters are required to configure the AI Block. The parameters are described below with example configurations shown at the end of this section.

CHANNEL

Select the channel that corresponds to the desired sensor measurement. The 644 measures both sensor temperature (channel 1) and terminal temperature (channel 2).

3-9

Page 31
Image 31
Emerson 644 manual Sensor Transducer Block, Analog Input AI Function Block, Damping, Configure the AI block, Channel