Rosemount 644

Reference Manual

00809-0400-4728, Rev AA June 2011

Parameters and Descriptions

The table below lists all of the configurable parameters of the Resource Block, including the descriptions and index numbers for each.

Table C-1. Resource Block Parameters and Descriptions

 

Index

 

Parameter

Number

Description

ACK_OPTION

38

Selection of whether alarms associated with the function block will be

 

 

automatically acknowledged.

ADVISE_ACTIVE

82

Enumerated list of advisory conditions within a device.

ADVISE_ALM

83

Alarm indicating advisory alarms. These conditions do not have a direct impact on the

 

 

process or device integrity.

ADVISE_ENABLE

80

Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE.

 

 

A bit on means that the corresponding alarm condition is enabled and will be detected. A

 

 

bit off means the corresponding alarm condition is disabled and will not be detected.

ADVISE_MASK

81

Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that

 

 

the condition is masked out from alarming.

ADVISE_PRI

79

Designates the alarming priority of the ADVISE_ALM

ALARM_SUM

37

The current alert status, unacknowledged states, unreported states, and disabled states

 

 

of the alarms associated with the function block.

ALERT_KEY

04

The identification number of the plant unit.

BLOCK_ALM

36

The block alarm is used for all configuration, hardware, connection failure or system

 

 

problems in the block. The cause of the alert is entered in the subcode field. The first alert

 

 

to become active will set the Active status in the Status parameter. As soon as the

 

 

Unreported status is cleared by the alert reporting task, another block alert may be

 

 

reported without clearing the Active status, if the subcode has changed.

BLOCK_ERR

06

This parameter reflects the error status associated with the hardware or software

 

 

components associated with a block. It is a bit string, so that multiple errors may be

 

 

shown.

CLR_FSTATE

30

Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has

 

 

cleared.

CONFIRM_TIME

33

The time the resource will wait for confirmation of receipt of a report before trying again.

 

 

Retry will not happen when CONFIRM_TIME=0.

CYCLE_SEL

20

Used to select the block execution method for this resource. The 644 supports the

 

 

following:

 

 

Scheduled: Blocks are only executed based on the function block schedule.

 

 

Block Execution: A block may be executed by linking to another blocks completion.

CYCLE_TYPE

19

Identifies the block execution methods available for this resource.

DD_RESOURCE

09

String identifying the tag of the resource which contains the Device Description for

 

 

this resource.

DD_REV

13

Revision of the DD associated with the resource - used by an interface device to locate

 

 

the DD file for the resource.

DEFINE_WRITE_LOCK

60

Allows the operator to select how WRITE_LOCK behaves. The initial value is “lock

 

 

everything”. If the value is set to “lock only physical device” then the resource and

 

 

transducer blocks of the device will be locked but changes to function blocks will be

 

 

allowed.

DETAILED_STATUS

55

Indicateds the state of the transmitter. See Resource Block detailed status codes.

DEV_REV

12

Manufacturer revision number associated with the resource - used by an interface device

 

 

to locate the DD file for the resource.

DEV_STRING

43

This is used to load new licensing into the device. The value can be written but will always

 

 

read back with a value of 0.

DEV_TYPE

11

Manufacturer’s model number associated with the resource - used by interface devices to

 

 

locate the DD file for the resource.

DIAG_OPTIONS

46

Indicates which diagnostics licensing options are enabled.

DISTRIBUTOR

42

Reserved for use as distributor ID. No Foundation enumerations defined at this time.

DOWNLOAD_MODE

67

Gives access to the boot block code for over-the-wire downloads.

 

 

0 = Uninitialized

 

 

1 = Run mode

 

 

2 = Download mode

C-2

Page 82
Image 82
Emerson 644 manual Parameters and Descriptions, Index