Rosemount 644
Reference Manual
Table
| Index |
|
|
|
|
|
Parameter | No. | Available Values | Units | Default | Read/Write | Description |
LO_ALM | 35 | Not applicable | None | Not applicable | Read only | The LO alarm data, which includes a value of the |
|
|
|
|
|
| alarm, a timestamp of occurrence and the state |
|
|
|
|
|
| of the alarm. |
LO_LIM | 30 | Out_Scale(2) | Out_Scale(2) | Not applicable | Read and Write | The setting for the alarm limit used to detect the |
|
|
|
|
|
| LO alarm condition. |
LO_LO_ALM | 36 | Not applicable | None | Not applicable | Read only | The LO LO alarm data, which includes a value of |
|
|
|
|
|
| the alarm, a timestamp of occurrence and the |
|
|
|
|
|
| state of the alarm. |
LO_LO_LIM | 32 | Out_Scale(2) | Out_Scale(2) | Not applicable | Read and Write | The setting for the alarm limit used to detect the |
|
|
|
|
|
| LO LO alarm condition. |
LO_LO_PRI | 31 | 0 – 15 | None | 1 | Read and Write | The priority of the LO LO alarm. |
LO_PRI | 29 | 0 – 15 | None | 1 | Read and Write | The priority of the LO alarm. |
LOW_CUT | 17 | > = 0 | Out_Scale(2) | 0 | Read and Write | If percentage value of transducer input fails |
|
|
|
|
|
| below this, PV = 0. |
MODE_BLK | 05 | Auto | None | Not applicable | Read and Write | The actual, target, permitted, and normal modes |
|
| Manual |
|
|
| of the block. |
|
| Out of Service |
|
|
| Target: The mode to “go to” |
|
|
|
|
|
| Actual: The mode the “block is currently in” |
|
|
|
|
|
| Permitted: Allowed modes that target may take |
|
|
|
|
|
| on |
|
|
|
|
|
| Normal: Most common mode for target |
OUT | 08 | Out_Scale(2) ± 10% | Out_Scale(2) | Not applicable | Read and Write | The block output value and status. |
OUT_D | 37 | Discrete_State 1 – 16 | None | Disabled | Read and Write | Discrete output to indicate a selected alarm |
|
|
|
|
|
| condition. |
OUT_SCALE | 11 | Any output range | All available | none | Read and Write | The high and low scale values, engineering units |
|
|
|
|
|
| code, and number of digits to the right of the |
|
|
|
|
|
| decimal point associated with OUT. |
PV | 07 | Not applicable | Out_Scale(2) | Not applicable | Read only | The process variable used in block execution. |
PV_FTIME | 18 | > = 0 | Seconds | 0 | Read and Write | The time constant of the |
|
|
|
|
|
| the time required for a 63% change in the IN |
|
|
|
|
|
| value. |
SIMULATE | 09 | Not applicable | None | Disable | Read and Write | A group of data that contains the current |
|
|
|
|
|
| transducer value and status, the simulated |
|
|
|
|
|
| transducer value and status, and the |
|
|
|
|
|
| enable/disable bit. |
ST_REV | 01 | Not applicable | None | 0 | Read only | The revision level of the static data associated |
|
|
|
|
|
| with the function block. The revision value will be |
|
|
|
|
|
| incremented each time a static parameter value |
|
|
|
|
|
| in the block is changed. |
STATUS_OPTS | 14 | Propagate fault forward |
| 0 | Read and Write |
|
|
| Uncertain if Limited |
|
|
|
|
|
| Bad if Limited |
|
|
|
|
|
| Uncertain if Man Mode |
|
|
|
|
STDDEV | 39 | 0 – 100 | Percent | 0 | Read and Write | The average absolute error between the PV and |
|
|
|
|
|
| its previous mean value over that evaluation time |
|
|
|
|
|
| defined by VAR_SCAN. |
STRATEGY | 03 | 0 – 65535 | None | 0 | Read and Write | The strategy field can be used to identify |
|
|
|
|
|
| grouping of blocks. This data is not checked or |
|
|
|
|
|
| processed by the block. |
TAG_DESC | 02 | 32 text characters | None | none | Read and Write | The user description of the intended application |
|
|
|
|
|
| of the block. |
UPDATE_EVT | 20 | Not applicable | None | Not applicable | Read only | This alert is generated by any change to the |
|
|
|
|
|
| static data. |
XD_SCALE | 10 | Any sensor range | inH2O (68 °F) | AI1(1): Customer |
| In all Rosemount devices the units of the |
|
|
| inHg (0 °C) | specification |
| transducer block is forced to match the unit code. |
|
|
| ftH2O (68 °F) |
|
|
|
|
|
| mmH2O (68 °F) | or |
|
|
|
|
| mmHg (0 °C) | inH2O (68 °F) for |
|
|
|
|
| psi |
|
| |
|
|
| bar | DP/GP rng 1, 2, 3) |
|
|
|
|
| mbar |
|
|
|
|
|
| g/cm2 | or |
|
|
|
|
| kg/cm2 |
|
|
|
|
|
| Pa | psi for DP/GP rng |
|
|
|
|
| kPa | 4, 5 AP/644 all rng |
|
|
|
|
| torr | AI2 deg C |
|
|
|
|
| atm |
|
| |
|
|
| deg C |
|
|
|
|
|
| deg F |
|
|
|
(1)The host system may write over default values
(2)Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale