Rosemount 644

Reference Manual

00809-0400-4728, Rev AA June 2011

Table C-3. Definitions of Analog Input Function Block System Parameters

 

Index

 

 

 

 

 

Parameter

No.

Available Values

Units

Default

Read/Write

Description

LO_ALM

35

Not applicable

None

Not applicable

Read only

The LO alarm data, which includes a value of the

 

 

 

 

 

 

alarm, a timestamp of occurrence and the state

 

 

 

 

 

 

of the alarm.

LO_LIM

30

Out_Scale(2)

Out_Scale(2)

Not applicable

Read and Write

The setting for the alarm limit used to detect the

 

 

 

 

 

 

LO alarm condition.

LO_LO_ALM

36

Not applicable

None

Not applicable

Read only

The LO LO alarm data, which includes a value of

 

 

 

 

 

 

the alarm, a timestamp of occurrence and the

 

 

 

 

 

 

state of the alarm.

LO_LO_LIM

32

Out_Scale(2)

Out_Scale(2)

Not applicable

Read and Write

The setting for the alarm limit used to detect the

 

 

 

 

 

 

LO LO alarm condition.

LO_LO_PRI

31

0 – 15

None

1

Read and Write

The priority of the LO LO alarm.

LO_PRI

29

0 – 15

None

1

Read and Write

The priority of the LO alarm.

LOW_CUT

17

> = 0

Out_Scale(2)

0

Read and Write

If percentage value of transducer input fails

 

 

 

 

 

 

below this, PV = 0.

MODE_BLK

05

Auto

None

Not applicable

Read and Write

The actual, target, permitted, and normal modes

 

 

Manual

 

 

 

of the block.

 

 

Out of Service

 

 

 

Target: The mode to “go to”

 

 

 

 

 

 

Actual: The mode the “block is currently in”

 

 

 

 

 

 

Permitted: Allowed modes that target may take

 

 

 

 

 

 

on

 

 

 

 

 

 

Normal: Most common mode for target

OUT

08

Out_Scale(2) ± 10%

Out_Scale(2)

Not applicable

Read and Write

The block output value and status.

OUT_D

37

Discrete_State 1 – 16

None

Disabled

Read and Write

Discrete output to indicate a selected alarm

 

 

 

 

 

 

condition.

OUT_SCALE

11

Any output range

All available

none

Read and Write

The high and low scale values, engineering units

 

 

 

 

 

 

code, and number of digits to the right of the

 

 

 

 

 

 

decimal point associated with OUT.

PV

07

Not applicable

Out_Scale(2)

Not applicable

Read only

The process variable used in block execution.

PV_FTIME

18

> = 0

Seconds

0

Read and Write

The time constant of the first-order PV filter. It is

 

 

 

 

 

 

the time required for a 63% change in the IN

 

 

 

 

 

 

value.

SIMULATE

09

Not applicable

None

Disable

Read and Write

A group of data that contains the current

 

 

 

 

 

 

transducer value and status, the simulated

 

 

 

 

 

 

transducer value and status, and the

 

 

 

 

 

 

enable/disable bit.

ST_REV

01

Not applicable

None

0

Read only

The revision level of the static data associated

 

 

 

 

 

 

with the function block. The revision value will be

 

 

 

 

 

 

incremented each time a static parameter value

 

 

 

 

 

 

in the block is changed.

STATUS_OPTS

14

Propagate fault forward

 

0

Read and Write

 

 

 

Uncertain if Limited

 

 

 

 

 

 

Bad if Limited

 

 

 

 

 

 

Uncertain if Man Mode

 

 

 

 

STDDEV

39

0 – 100

Percent

0

Read and Write

The average absolute error between the PV and

 

 

 

 

 

 

its previous mean value over that evaluation time

 

 

 

 

 

 

defined by VAR_SCAN.

STRATEGY

03

0 – 65535

None

0

Read and Write

The strategy field can be used to identify

 

 

 

 

 

 

grouping of blocks. This data is not checked or

 

 

 

 

 

 

processed by the block.

TAG_DESC

02

32 text characters

None

none

Read and Write

The user description of the intended application

 

 

 

 

 

 

of the block.

UPDATE_EVT

20

Not applicable

None

Not applicable

Read only

This alert is generated by any change to the

 

 

 

 

 

 

static data.

XD_SCALE

10

Any sensor range

inH2O (68 °F)

AI1(1): Customer

 

In all Rosemount devices the units of the

 

 

 

inHg (0 °C)

specification

 

transducer block is forced to match the unit code.

 

 

 

ftH2O (68 °F)

 

 

 

 

 

 

mmH2O (68 °F)

or

 

 

 

 

 

mmHg (0 °C)

inH2O (68 °F) for

 

 

 

 

 

psi

 

 

 

 

 

bar

DP/GP rng 1, 2, 3)

 

 

 

 

 

mbar

 

 

 

 

 

 

g/cm2

or

 

 

 

 

 

kg/cm2

 

 

 

 

 

 

Pa

psi for DP/GP rng

 

 

 

 

 

kPa

4, 5 AP/644 all rng

 

 

 

 

 

torr

AI2 deg C

 

 

 

 

 

atm

 

 

 

 

 

deg C

 

 

 

 

 

 

deg F

 

 

 

(1)The host system may write over default values pre-configured by Rosemount Inc.

(2)Assume that when L_Type = Direct, the user configures Out_Scale which is equal to XD_Scale

C-10

Page 90
Image 90
Emerson 644 manual Lolopri