Quick Installation Guide

Rosemount 8712 / 8700 Series

00825-0100-4664, Rev BB January 2013

STEP 6 CONTINUED...

To order cable specify length as quantity desired. 25 feet = Qty (25) 08732-0753-1003

Table 7. Cable Requirements

 

 

Description

Length

Part Number

Coil Drive Cable (14 AWG)

ft

08712-0060-0001

Belden 8720, Alpha 2442

m

08712-0060-2013

or equivalent

 

 

Signal Cable (20 AWG)

ft

08712-0061-0001

Belden 8762, Alpha 2411

m

08712-0061-2003

or equivalent

 

 

Combination Cable

ft

08732-0753-1003

Coil Drive Cable (18 AWG) and

m

08732-0753-2004

Signal Cable (20 AWG)

 

 

WARNING

Potential Shock Hazard Across Terminals 1 & 2 (40 Vac).

Wiring the Transmitter to the Sensor

When using individual cables for coil drive and signal refer to Table 8. If using the combination coil drive and signal cable, refer to Table 9. See Figure 16 for transmitter specific wiring diagram.

1.Connect the coil drive cable using terminals 1, 2, and 3 (ground).

2.Connect the signal cable using terminals 17, 18, and 19.

Table 8. Individual Coil and Signal Cables

 

 

Transmitter Terminal

Sensor Terminal

Wire Gauge

Wire Color

1

1

14

Clear

2

2

14

Black

3 or Ground

3 or Ground

14

Shield

17

17

20

Shield

18

18

20

Black

19

19

20

Clear

Table 9. Combination Coil and Signal Cable

 

 

Transmitter Terminal

Sensor Terminal

Wire Gauge

Wire Color

1

1

18

Red

2

2

18

Green

3 or Ground

3 or Ground

18

Shield

17

17

20

Shield

18

18

20

Black

19

19

20

White