Quick Installation Guide
00825-0100-4664, Rev BB
January 2013 Rosemount 8712 / 8700 Series
7
STEP 3: MOUNTING

Upstream/Downstream Piping

To ensure specification accuracy over widely varying process conditions, install the sensor a
minimum of five straight pipe diameters upstream and two pipe diameters downstream from
the electrode plane (see Figure3).
Installations with reduced straight runs from 0 to 5 pipe diameters are possible. In reduced
straight pipe run installations, performance will shift to as much as 0.5% of rate. Reported
flow rates will still be highly repeatable.

Flow Direction

The sensor should be mounted so the FORWARD end of the flow arrow, shown on the
sensor identification tag, points in the direction of flow through the sensor.

Sensor Orientation

The sensor should be installed in a position that ensures the sensor remains full during
operation. Vertical installation allows upward process fluid flow and keeps the
cross-sectional area full, regardless of flow rate. Horizontal installation should be restricted
to low piping sections that are normally full. In these cases, orient the electrode plane to
within 45° of horizontal.
Figure 3. Upstream and Downstream StraightPipe Diameters
5 Pipe Diameters 2 Pipe Diameters
Flow
4664RevBBQIG.fm Page 7 Friday, January 11, 2013 6:13 PM