Configuration

7.0CONFIGURATION

The Liebert GXT2-PP20KRT208 parallel POD allows connecting a maximum of three UPSs in paral- lel. See the following table for the maximum output power.

Table 2

Maximum output power from paralleled UPSs

 

 

 

 

 

 

 

Method

Number of UPSs

Maximum Output Power

Redundancy

 

 

 

 

Paralleling for Capacity

2

20kVA

 

 

 

 

Paralleling for Capacity

3

20kVA

10kVA

and Redundancy

 

 

 

7.1Paralleling for Capacity

When two UPSs are connected to the paralleling system, the maximum output power is 20kVA. Each UPS supplies 10kVA of output power. Redundant power is not available if either of the paralleled the UPSs fails.

7.2Paralleling for Capacity and Redundancy

When three UPSs are connected to the paralleling system, the maximum output power is 20kVA. plus redundancy of one 10kVA UPS. This setup permits that the paralleling system to operate normally even if one of the UPSs fails or runs out of battery power.

For the paralleling procedures, see 5.0 - Installation.