Configuration
7.0CONFIGURATION
The Liebert
Table 2 | Maximum output power from paralleled UPSs |
| |||
|
|
|
|
| |
| Method | Number of UPSs | Maximum Output Power | Redundancy | |
|
|
|
| ||
Paralleling for Capacity | 2 | 20kVA | — | ||
|
|
|
| ||
Paralleling for Capacity | 3 | 20kVA | 10kVA | ||
and Redundancy | |||||
|
|
|
7.1Paralleling for Capacity
When two UPSs are connected to the paralleling system, the maximum output power is 20kVA. Each UPS supplies 10kVA of output power. Redundant power is not available if either of the paralleled the UPSs fails.
7.2Paralleling for Capacity and Redundancy
When three UPSs are connected to the paralleling system, the maximum output power is 20kVA. plus redundancy of one 10kVA UPS. This setup permits that the paralleling system to operate normally even if one of the UPSs fails or runs out of battery power.
For the paralleling procedures, see 5.0 - Installation.