Emerson GXT2-PP20KRT208 Main Input and Output Terminal Block Connections, Electrical requirements

Models: GXT2-PP20KRT208

1 36
Download 36 pages 49.11 Kb
Page 19
Image 19

Installation

5.3Main Input and Output Terminal Block Connections

Conduit entry holes are provided on the front top of the removable cover plate for the parallel POD. Input and output wiring should be run in separate conduit. See the following requirements and label to connect the wires.

Table 1

Electrical requirements

 

 

 

 

 

 

 

 

 

 

Recommended Wire

 

Input Current

Recommended Maximum

(including ground wire)

Terminal

Rating

 

External Overcurrent Protection

(75°C copper wire)

Tightening Torque

83A

 

120A

1/0 AWG

50 lb-in (5.6 N-m)

 

 

 

 

 

Figure 11 Hardwire terminal connections

Green

Red

 

 

Black

Green

L2

N

L1

L2

N

 

L1

OUTPUT

 

INPUT

120 Amp Max Branch

 

Overcurrent Protection

NOTE

Terminal blocks are color-coded for easy installation. Make sure that the wires are connected to the correct terminals. A 3/16" hex wrench is required for tightening the terminal blocks.

When the terminal block connections are done, secure the cover plate with seven screws.

Figure 12 Secure the cover plate over the terminal connections