Installation

5.4Add an Output Power Distribution Module—Optional

! WARNING

Risk of electric shock. Can cause equipment damage, injury or death.

Lethal voltages may exist within the UPS and parallel POD as long as the UPS is connected.

Before beginning to install the optional output distribution module, make sure the paralleling system and all connected UPSs are completely powered off.

To add an optional output distribution module to the Liebert GXT2-PP20KRT208:

1.Disconnect and secure utility power from the parallel POD and completely power Off all connected UPSs.

2.Remove the four screws securing the blank output distribution cover plate of the parallel POD.

3.Set the screws aside to attach an output distribution module to the parallel POD.

4.Snap together the color-coded, mating electrical connectors of the optional output distribution module to the parallel POD.

5.Use the screws removed in Step 2 to attach the output distribution module to the distribution module to the parallel POD.

Screw holes to attach

to parallel POD

Electrical connector snaps to connector inside parallel POD

Optional output power

Screw holes to attach

Install the optional output

power distribution module

to parallel POD

distribution module

in the parallel POD

 

(PD-202 shown)

 

 

NOTE

The Liebert GXT2-PP20KRT208 distribution POD options are different than the distribution PODs used with individual Liebert GXT2-10000RT208 UPSs. Each POD type has different connectors and are not interchangeable.

If a Liebert GXT2-10000RT208 UPS that is to be connected to the parallel POD has a distribution POD option, then the distribution POD must be removed from the UPS to connect the parallel power cable assembly to the UPS.