Emerson GXT2-PP20KRT208 user manual UPS Configuration Settings

Models: GXT2-PP20KRT208

1 36
Download 36 pages 49.11 Kb
Page 32
Image 32

Communication

9.3UPS Configuration Settings

Refer to the Liebert GXT2-10000RT208 user manual, SL-23444, for additional information on using the UPS Configuration Program.

When the configuration program is used with any of the connected Liebert GXT2-10000RT208 UPSs, options selected are changed in all operational UPSs connected to the parallel POD with the parallel communication cable.

If only one UPS is operational, or if any parallel communication cables are removed from the parallel POD, then options selected with the configuration program will be made only it that operational UPS.

NOTICE

Risk of improper configuration. May cause equipment damage.

All UPSs operating in a parallel mode must have their output voltages configured for the same value. Operating in parallel mode with UPSs configured for different output voltages may damage the UPSs.

When optional settings are selected, such as the Auto-restart delay, the same configuration choice must be made on all connected UPSs. This permits all UPSs connected to the parallel POD to operate in the same manner.

28

Page 32
Image 32
Emerson GXT2-PP20KRT208 user manual UPS Configuration Settings