SAG582135000 |
|
|
|
|
| System Application Guide | ||||||
Issue AE, January 31, 2007 |
|
|
|
| Spec. No. 582135000 (Model LXP48F1) | |||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Home | |
|
|
|
|
| Recm 90°C Wire Size (1) |
|
|
|
| |||
| Fuse/Circuit |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
| Breaker |
| 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 6 AWG | 4 AWG | 2 AWG |
| |
| Amperage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Loop Length (feet) (2) |
|
|
|
| ||||
|
|
|
|
|
|
|
|
| ||||
| 1, 3, 5, |
| 37 (3, 4, 5) | 58 (3, 4, 5) | 93 (3, 4, 5) | 148 (3, 4, 5) |
| 236 (3, 4, 5) | 376 (3, 4, 5) | 597 (3, 4, 5) |
| |
| 6, 10A |
|
|
|
|
|
|
|
|
|
|
|
| 15A |
| 24 (3, 4) | 39 (3, 4, 5) | 62 (3, 4, 5) | 99 (3, 4, 5) |
| 157 (3, 4, 5) | 250 (3, 4, 5) | 398 (3, 4, 5) |
| |
| 20A |
| 29 (3, 4) | 46 (3, 4, 5) | 74 (3, 4, 5) |
| 118 (3, 4, 5) | 188 (3, 4, 5) | 298 (3, 4, 5) |
| ||
| 25A |
| 37 (3, 4,) | 59 (3, 4, 5) |
| 94 (3, 4, 5) | 150 (3, 4, 5) | 239 (3, 4, 5) |
| |||
| 30A |
| 31 (3, 4) | 49 (3, 4, 5) |
| 78 (3, 4, 5) | 125 (3, 4, 5) | 199 (3, 4, 5) |
| |||
| 35A |
| 42 (3, 4) |
| 67 (3, 4, 5) | 107 (3, 4, 5) | 170 (3, 4, 5) |
| ||||
| 40A |
| 37 (3, 4) |
| 59 (3, 4, 5) | 94 (3, 4, 5) | 149 (3, 4, 5) |
| ||||
| 45A |
| 33 (3, 4) |
| 52 (3, 4) | 83 (3, 4) | 132 (3, 4) |
| ||||
| 50A |
| 29 (3) |
| 47 (3, 4,) | 75 (3, 4) | 119 (3, 4) |
| ||||
| 60A |
|
| 39 (3, 4) | 62 (3, 4) | 99 (3, 4) |
| |||||
| 70A |
|
| 53 (3, 4) | 85 (3, 4) |
| ||||||
| 75A |
|
| 50 (3, 4) | 79 (3, 4) |
| ||||||
| 80A |
|
| 47 (3) | 74 (3, 4) |
| ||||||
| 90A |
|
| 66 (3, 4) |
| |||||||
| 100A |
|
| 59 (3, 4) |
| |||||||
|
|
|
| Recommended Crimp Lug (6) |
|
|
|
|
| |||
| Load Lug |
| 245312200 | 245312400 | 245312400 | 245350400 |
| 245350600 | 245350700 | 245350800 |
| |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| Return Lug |
| 245342300 | 245342300 | 245342300 | 245390200 |
| 245346700 | 245346800 | 245346900 |
| |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Table 4 |
|
|
|
|
| ||
|
|
| Recommended Distribution (Load) Wire Size and Lug Selection for |
|
|
| ||||||
|
| TLS/TPS Fuse and Bullet |
|
|
|
Notes to Tables 4:
1Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table
2Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
4Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.
Page 24 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.