Download 43 pages 44.31 Kb
Page 9
Image 9
Ampere

System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

4)Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for battery clearance. See table above.

5)Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be furnished with or without Battery Disconnect circuit breakers as specified for the first tray ordered.

Home

6) If ordering List 93 with circuit breakers, order one (1) circuit breaker per List 93 from the following table.

Ampere

Part Number

 

Rating

 

 

 

Electrical/Mechanical Trip1 (Black Handle)

 

Electrical Trip2 (White Handle)

50

256694300

 

256694400

60

256694700

 

256694800

70

256695100

 

256695200

75

256695500

 

256695600

100

256695900

 

256696000

125

100765

 

100762

150

100763

 

100764

200

121810

 

121809

Circuit Breaker Alarm Operation:

1Provides an alarm during an electrical or manual trip condition.

2Provides an alarm during an electrical trip condition only.

7)If ordering List 93 with circuit breakers, specify breaker mounting on left side or right side of tray.

Restrictions

Maximum number of List 93’s per bay is five (5).

A single List 93 must mount at bottom of bay. Multiple List 93’s must mount starting at bottom of bay and working upward.

Page 9 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 9