System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

 

 

 

 

 

Home

List LD: Distribution Cabinet

(18)Fuse/Circuit Breaker System Positions with Low Voltage Load Disconnect and Load Shunt

Features

Single Voltage Distribution (-48V)

Maximum Capacity: Input: 500A max.

Total Distribution: 300A max.

Battery Recharge Current: 500A max. @ +50°C; 400A @ +65°C.

Battery Terminals as Remote Feed: 200A max.

(18) Mounting Positions for Load Distribution Fuses or Circuit Breakers, or accepts Alarm-Type Fuse Distribution Assembly (Kit P/N 524679).

Accepts TPS/TLS-Type Fuses (3 to 100A) or Bullet Nose Type Circuit Breakers (1 to 100A)

Caution: A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device.

Caution: The maximum size circuit breaker or fuse used in ambient temperatures above +50°C ambient shall be 40 amperes.

Includes (1) Low Voltage Load Disconnect Contactor (LVLD)

Includes and (1) Load Shunt (total distribution load)

See Distribution Cabinet Electrical Connection Locations and Dimensions.

Restrictions

The maximum number of Distribution Cabinets in a system is three (3). Each Distribution Cabinet must be mounted immediately above a Power Shelf with zero (0) inches of rack space between units to accommodate the furnished busbar links. Adequate vertical mounting space must be provided above each Distribution Cabinet to accommodate distribution and battery cabling.

Fuses and/or circuit breakers are to be mounted from right to left, starting with the highest capacity and working to the lowest capacity.

Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.

Ordering Notes

1)Order circuit breakers, as required, per Table 1.

2)Order fuses, as required, per Tables 2.

3)Order one (1) Part No. 117201 fuseholder per fuse ordered in 2) above.

4)Order one (1) Part No. 524690 mounting kit per circuit breaker or fuseholder ordered in 1) or 3) above. Kit includes bullet socket busbar and hardware for mounting load and return lugs for one distribution position.

5)Order one (1) Load lug (one-hole, 1/4” bolt clearance hole) and one (1) Load Return lug (two-hole, 1/4” bolt clearance holes on 5/8” centers) as required for each distribution position per Table 4.

Page 15 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 15
Image 15
Emerson LXP48F1 manual Home

LXP48F1 specifications

The Emerson LXP48F1 is a versatile and powerful HVAC solution designed for both residential and commercial applications. This unit stands out for its efficient performance and advanced features, making it a popular choice among HVAC professionals and end-users alike.

One of the key features of the LXP48F1 is its variable-speed compressor technology. This innovative feature allows the unit to operate at different speeds depending on the heating or cooling demand. By adjusting its output, the LXP48F1 ensures optimal comfort while minimizing energy consumption. This results in lower electricity bills and a reduced carbon footprint, making it an environmentally friendly option.

The LXP48F1 is also equipped with a robust HVAC control system that enhances its efficiency and performance. The onboard microprocessor continuously monitors system performance and makes real-time adjustments to optimize operation. This smart control technology not only improves comfort levels but also extends the lifespan of the unit by preventing undue stress on its components.

Another notable aspect of the LXP48F1 is its compact and sleek design, making it suitable for installation in various spaces. Whether it’s a tight attic or a small basement, the LXP48F1 is built to fit seamlessly into different environments without compromising functionality.

The unit boasts excellent sound attenuation features, allowing for quiet operation during heating and cooling cycles. This is particularly important in residential settings where noise can be a significant concern. The LXP48F1 operates quietly, ensuring a comfortable environment without disruptive sounds.

Emerson has also integrated advanced refrigerant management technology into the LXP48F1. Designed to work with modern refrigerants, the unit complies with environmental regulations while ensuring effective cooling performance. The ability to manage refrigerant flow efficiently is crucial for maintaining consistent temperature control.

In terms of reliability, the LXP48F1 is constructed with high-quality materials and components designed to withstand the rigors of daily use. The unit comes with a warranty, reflecting Emerson’s confidence in the durability and performance of the product.

In summary, the Emerson LXP48F1 is a leading HVAC solution that combines advanced technology, energy efficiency, and user-friendly features. Its variable-speed compressor, smart control system, quiet operation, and robust design make it an ideal choice for those seeking an effective heating and cooling solution for various applications. With Emerson’s reputation for quality and reliability, the LXP48F1 is a sound investment for any property.