Emerson LXP48F1 SAG582135000, Ambient, Loop, Recm 90C, Current, Operating, Length Ft, Crimp Lug

Models: LXP48F1

1 43
Download 43 pages 44.31 Kb
Page 27
Image 27
Manual background

System Application Guide

 

 

 

 

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

 

Issue AE, January 31, 2007

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

Ambient

Loop

Loop

Recm 90°C

Recommended

 

 

Current

Operating

Length (Ft)

Length (Ft)

 

 

Wire Size

(1)

Crimp Lug

(3)

 

 

(Amps)

Temperature (1)

1.0 Volt Drop (2)

0.25 Volt Drop (2)

 

 

 

 

163

40°C

36

9

(1) 2 AWG

(1) 245350800

 

 

155

50°C

38

9

(1) 2 AWG

(1) 245350800

 

 

110

65°C

54

13

(1) 2 AWG

(1) 245350800

 

Table 5

Recommended Battery Wire Size and Lug Selection

Notes to Tables 5:

1Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17(Single-Insulated Copper Conductors in Free Air) for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C and 65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.

2Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the sum of the lengths of the positive and negative leads.

3Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.