Emerson LXP48F1 List GA Distribution Cabinet, GMT Fuse System Positions with Split Bus Features

Models: LXP48F1

1 43
Download 43 pages 44.31 Kb
Page 13
Image 13
List GA: Distribution Cabinet

System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

List GA: Distribution Cabinet

(20)GMT Fuse System Positions with Split Bus

Features

Home

List of Parts

Single Voltage Distribution (-48V)

Maximum Capacity: Input: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.

Total Distribution: 30A per bus, 60A total @ +65°C

Battery Recharge Current: 163A @ +40°C; 155A @ 50°C; 110A @ +65°C.

Battery Terminals as Remote Feed: 103A @ +40°C; 95A @ 50°C; 50A @ +65°C.

(20) Mounting Positions for Alarm-Type Load Distribution Fuses, (10) per bus.

Accepts GMT-Type Fuses (1/4A to 15A).

Includes (20) dummy fuses equipped with safety fuse covers.

Provides local and external fuse alarm.

See Distribution Cabinet Electrical Connection Locations and Dimensions.

Restrictions

Maximum distribution fuse size: 15A

Maximum size wire each fuse position accepts is 14 AWG. Input is cable-fed only.

Maximum size wire input terminals accept is (1) 2 AWG per polarity. No load or battery shunts are provided.

Ordering Notes

1)Order fuses, as required, per Tables 3.