Recommended Wired Size and Lugs

System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

Recommended Wired Size and Lugs

Distribution (Load) Wire Sizes and Lugs—List BD, BL, BS, LB, LD, LS, LX Features

Home

In each Distribution Cabinet, lug-terminated load conductors are connected to the distribution fuseholder or circuit breaker mounting positions and the ground busbar. The distribution fuseholder or circuit breaker mounting positions provide 1/4-20 threaded holes for installation of customer-provided one-hole lugs that have 1/4 in. bolt clearance holes. The ground busbar provides 1/4-20 threaded holes for installation of customer-provided two-hole lugs that have 1/4 in. bolt clearance holes on 5/8” centers. Factory provides lug- mounting hardware for the distribution fuseholder or circuit breaker positions and distribution ground busbar.

For lug mounting hole size and spacing dimensions, refer to Electrical Connection Locations and Dimensions under Physical Size Information in this document. Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG.

Restrictions

All lugs for customer connections must be ordered separately.

Ordering Notes

1)The rating of the distribution device determines the wire size requirements. For wire size and lug selection, refer to Table 4.

2)For other available lugs and hardware, refer to drawings 031110100 through 031110300.