Emerson LXP48F1 Ambient, Loop, Recm 90C, Current, Operating, Length Ft, Crimp Lug, Amps, List GA

Models: LXP48F1

1 43
Download 43 pages 44.31 Kb
Page 26
Image 26
Ambient

SAG582135000

 

 

 

 

System Application Guide

Issue AE, January 31, 2007

 

Spec. No. 582135000 (Model LXP48F1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Home

 

 

 

 

 

 

 

 

 

 

 

 

Maximum

Ambient

Loop

Loop

Recm 90°C

Recommended

 

 

Current

Operating

Length (Ft)

Length (Ft)

 

 

Wire Size

(1)

Crimp Lug

(3)

 

 

(Amps)

Temperature (1)

1.0 Volt Drop (2)

0.25 Volt Drop (2)

 

 

 

 

 

 

 

List BB, BD, BL, BS, LB, LD, LS, LX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

40°C

37

9

(3) 4 AWG

(3) 245346800

 

 

59

14

(3) 2 AWG

(3) 245350800

 

 

 

 

 

 

500

50°C

37

9

(3) 4 AWG

(3) 245346800

 

 

59

14

(3) 2 AWG

(3) 245350800

 

 

 

 

 

 

400

65°C

59

14

(3) 2 AWG

(3) 245350800

 

 

 

 

List GA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

163

40°C

36

9

(1) 2 AWG

(1) 245350800

 

 

155

50°C

38

9

(1) 2 AWG

(1) 245350800

 

 

110

65°C

54

13

(1) 2 AWG

(1) 245350800

 

Table 5

Recommended Battery Wire Size and Lug Selection

Notes to Tables 5:

1Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-17(Single-Insulated Copper Conductors in Free Air) for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C and 65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.

2Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the sum of the lengths of the positive and negative leads.

3Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping information.

DC Input Wire Sizes and Lugs—List GA

Features

In the List GA Distribution Cabinet, lug-terminated battery conductors are connected to the battery terminals. Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of customer provided two-hole lugs.

For lug mounting hole size and spacing dimensions, refer to the illustration provided in the Physical Size Information section.

Restrictions

All lugs for customer connections must be ordered separately. Customer must supply lug-mounting hardware.

Ordering Notes

1)Refer to Table 5 for recommended wire sizes and lugs at rated maximum Distribution Cabinet load. When making connections, observe correct polarity.

2)For other available lugs and hardware, refer to drawings 031110100 through 031110300.

Page 26 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 26
Image 26
Emerson LXP48F1 Ambient, Loop, Recm 90C, Current, Operating, Length Ft, Crimp Lug, Amps, Volt Drop, List GA, SAG582135000