SAG582135000 |
|
|
|
| System Application Guide | |||||
Issue AE, January 31, 2007 |
| Spec. No. 582135000 (Model LXP48F1) | ||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| Home | |
|
|
|
|
|
|
|
|
|
|
|
| Maximum | Ambient | Loop | Loop | Recm 90°C | Recommended |
| |||
| Current | Operating | Length (Ft) | Length (Ft) |
| |||||
| Wire Size | (1) | Crimp Lug | (3) |
| |||||
| (Amps) | Temperature (1) | 1.0 Volt Drop (2) | 0.25 Volt Drop (2) |
|
|
|
| ||
|
|
| List BB, BD, BL, BS, LB, LD, LS, LX |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
| 500 | 40°C | 37 | 9 | (3) 4 AWG | (3) 245346800 |
| |||
| 59 | 14 | (3) 2 AWG | (3) 245350800 |
| |||||
|
|
|
| |||||||
| 500 | 50°C | 37 | 9 | (3) 4 AWG | (3) 245346800 |
| |||
| 59 | 14 | (3) 2 AWG | (3) 245350800 |
| |||||
|
|
|
| |||||||
| 400 | 65°C | 59 | 14 | (3) 2 AWG | (3) 245350800 |
| |||
|
|
| List GA |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
| 163 | 40°C | 36 | 9 | (1) 2 AWG | (1) 245350800 |
| |||
| 155 | 50°C | 38 | 9 | (1) 2 AWG | (1) 245350800 |
| |||
| 110 | 65°C | 54 | 13 | (1) 2 AWG | (1) 245350800 |
|
Table 5
Recommended Battery Wire Size and Lug Selection
Notes to Tables 5:
1Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table
2Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or less, at rated full load output current of the shelf for the loop lengths shown in this column. Loop length is the sum of the lengths of the positive and negative leads.
3
DC Input Wire Sizes and Lugs—List GA
Features
♦In the List GA Distribution Cabinet,
♦For lug mounting hole size and spacing dimensions, refer to the illustration provided in the Physical Size Information section.
Restrictions
All lugs for customer connections must be ordered separately. Customer must supply
Ordering Notes
1)Refer to Table 5 for recommended wire sizes and lugs at rated maximum Distribution Cabinet load. When making connections, observe correct polarity.
2)For other available lugs and hardware, refer to drawings 031110100 through 031110300.
Page 26 of 43
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.