Emerson LXP48F1 manual Distribution Load Wire Sizes and Lugs-List GA Features, SAG582135000, Home

Models: LXP48F1

1 43
Download 43 pages 44.31 Kb
Page 25
Image 25
Distribution (Load) Wire Sizes and Lugs—List GA

System Application Guide

SAG582135000

Spec. No. 582135000 (Model LXP48F1)

Issue AE, January 31, 2007

5Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature.

6Load lugs are one-hole for 1/4" bolt clearance. Load Return lugs are two-hole for 1/4" bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping information.

Home

Distribution (Load) Wire Sizes and Lugs—List GA

Features

In each List GA Distribution Cabinet, Screw compression terminals are provided for connecting Load and Load Return wiring. Maximum size of wire to be connected to a single position is 14 AWG.

Battery Wire Sizes and Lugs—All Lists

Features

List BD, BL, BS, LB, LD, LS, LX: In each Distribution Cabinet, lug-terminated battery conductors are connected to the battery terminals. Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of customer provided two-hole lugs.

List GA: In each Distribution Cabinet, lug-terminated battery conductors are connected to the battery terminals. Captive nuts, (1/4-20 on 5/8" centers) are provided for installation of customer provided two-hole lugs.

For lug mounting hole size and spacing dimensions, refer to the illustration provided in the Physical Size Information section.

Restrictions

All lugs for customer connections must be ordered separately. Customer must supply lug-mounting hardware.

Ordering Notes

1)Battery wire size varies depending on load, therefore no specific information is provided for wire size. Refer to Table 5 for recommended wire sizes and lugs at rated maximum Distribution Cabinet load. When making connections, observe correct polarity.

2)For other available lugs and hardware, refer to drawings 031110100 through 031110300.

Page 25 of 43

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 25
Image 25
Emerson LXP48F1 Distribution Load Wire Sizes and Lugs-List GA Features, Battery Wire Sizes and Lugs-All Lists Features