4. Installation

DANGER

Dangers during Installation

Risk of injury / Risk of damage to the device or plant

Observe all safety regulations in the chapter “Safety”.

4.1 Connection terminals (overview)

Tab.1 Connecting terminals (overview)

Terminal

X11

X1 - X8

.1

.2

.3

.1

.2

.3

.4

.5

.6

.7

Description

24V (+)

24V (ground)

grounding, carry out as short as possible jointly switchable ground potential RxD

TxD ground

separately switchable ground potential ground

ground potential for shield connection

Connection diagram see page 30.

4.2Connecting a 24 V power supply

>Switch off the main power supply including the external 24 V power source and make sure these cannot be accidentally switched back on again.

>Connect the external 24 V voltage supply (150 mA) to X11.1 (+) and X11.2 (-) (reverse polarity protec- tion).

>Ground the X11.3 terminal by as short a route as possible (for EMC reasons).

REMARK

24 V DC power source

Several bus modules can be operated with one power supply.

>In cases of SELV (safety extra low voltages) do not ground the 24 V power source.

4.3Connecting the power controller to X1-X8

>Switch off the main power supply including the external 24 V power source and make sure these cannot be accidentally switched back on again.

>Connect the interfaces X1 to X8 of the bus module to the system interfaces of the power controller (shielded four-wire cable)

Attention: To control all parameters by ProfiNet we recommend closing the Thyro-A switches S1.3, S1.4, S1.5 (Thyro-Tool Mode).

4.4 Connecting the Ethernet bus module to the master

The Ethernet bus module has two Ethernet ports which are equipped with a switch functionality which allows a line topology to be constructed.

A standard patch cable is required for connecting with a switch. For a direct connection (line topology) a cross-over cable is required.