6. Operation
6.1 Start configuration (parameterization)
Via the parameterization (in step 7 – HW Config,
No connection (slot 1-8):
Here you can set what should happen with the output data of the devices if the connection to the master is interrupted.
Hold last values | The output data are not changed. |
Outputs = 0 | The output data are set to 0 |
No connection (slot 9):
Here you can set what should happen with the output data of the bus module if the connection to the master is interrupted.
Hold last value | The digital outputs are not changed. |
Outputs = 0 | The digital outputs are set to 0. |
Averaging of the measured values:
Here you can enter the number of actual values which flow into the averaging. A new value is calculated once a second. Values from
Remove device when it is switched off:
Not all devices are equipped with a 24 V supply connection. When switching off the Thyro mains supply and the control voltage supply (24V) the Thyro no longer communicates with the bus modules. A switched off device will normally be displayed as pull. This display can be suppressed here.
Deactivate | Devices which are no longer accessible (no communication) will continue to |
| be displayed as plug. |
Activate | Devices which are no longer accessible will be displayed as pull. |
Use output data:
The suppression of certain output data can be activated here.
Always | New output data are transferred immediately. |
Only when Bit is set | New output data are only transferred, if the Bit 0 is set in the output |
| “Functions” |
6.2 Cyclical data transmission (configuration)
The configuration of the cyclical data traffic is undertaken by adding modules.
The input and output data depend on the device types. The following tables show the input and output data available for each of the devices.
6.3 Input and output data Thyro-S