17
Tab. 8 Cyclic input and output data with Thyro-A 1A...HRLP1Tab. 9 Cyclic input and output data with Thyro-A 2A...H1Tab. 10 Cyclic input and output data with Thyro-A 2A...HRL1
Offset Input data, actual values Data type Size Unit
0 Load voltage L1 float 4 [V]
4 Load current L1 float 4 [A]
8 Power L1 float 4 [W]
12 Mains voltage L1 integer 2 [V]
14 Switch-on time TS integer 2 [period]
16 Switch-on angle alpha integer 2 [0.01 °el]
18 Total setpoint integer 2 4096=100%
20 Fault (see table 14b) integer 2 -
22 Status (see table 14b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Master setpoint integer 2 4096=100%
Offset Input data, actual values Data type Size Unit
0 Load voltage L1 float 4 [V]
4 Load voltage L3 float 4 [V]
8 Mains voltage L1 integer 2 [V]
10 Mains voltage L3 integer 2 [V]
12 Switch-on time TS integer 2 [period]
14 Total setpoint integer 2 4096=100%
16 Fault (see table 14b) integer 2 -
18 Status (see table 14b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Master setpoint integer 2 4096=100%
Offset Input data, actual values Data type Size Unit
0 Load voltage L1 float 4 [V]
4 Load voltage L3 float 4 [V]
8 Load current L1 float 4 [A]
12 Load current L2 float 4 [A]
16 Load current L3 float 4 [A]
20 Mains voltage L1 integer 2 [V]
22 Mains voltage L3 integer 2 [V]
24 Switch-on time TS integer 2 [period]
26 Total setpoint integer 2 4096=100%
28 Fault (see table 14b) integer 2 -
30 Status (see table 14b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Master setpoint integer 2 4096=100%