6.8 Input and output data Thyro-Measurement Unit

Tab. 25 Cyclic input and output data TMU mode

Offset

Input data, actual values

Data type

Size

Unit

0

AC input 1

float

4

[A],[V]

4

AC input 2

float

4

[A],[V]

8

AC input 3

float

4

[A],[V]

12

Power

float

4

[W]

16

Energy

float

4

[kWh]

20

DC input 1

integer

2

4096=100%

22

DC input 2

integer

2

4096=100%

24

DC input 3

integer

2

4096=100%

26

Mains voltage

integer

2

[V]

28

Period duration

integer

2

[μs]

30

Temperature

integer

2

[°C]

32

Fault (see table 25b)

integer

2

-

34

Status (see table 25b)

integer

2

-

Tab. 25b Status TPM, TSC, TIO, TMU

Description

Bit

Fault LED, fault output*

Frequency measurement outside of 47Hz to 63Hz

Bit 0

on

SYNC error, no cero crossing within the gate

Bit 1

on

Temperature max. limit has been exceeded

Bit 2

on

Temperature min. limit has been exceeded

Bit 3

on

One or more parameters outside the limits

Bit 4

on

Mains voltage lower than lower voltage limit

Bit 5

on

Tab. 25b Fault TPM, TSC, TIO, TMU

Description

Bit

Alarm LED, alarm output*

Mains frequency is 60Hz

Bit 2

off

Transformer 1 fallen below min. limit

Bit 3

on

Transformer 1 exceeded max. limit

Bit 4

on

Transformer 2 fallen below min. limit

Bit 5

on

Transformer 2 exceeded max. limit

Bit 6

on

Transformer 3 fallen below min. limit

Bit 7

on

Transformer 3 exceeded max. limit

Bit 8

on

Device switched off

Bit 9

--

Wrong device

Bit 10

--

Bus module active (0=no bus module / 1=bus module

Bit 11

off

active)

 

 

* Default setting can be parameterized.

 

 

25

Page 25
Image 25
AEG Thyro-S H1 manual Input and output data Thyro-Measurement Unit, Tab Cyclic input and output data TMU mode