Tab. 5b Thyro-S Status

Description

Bit

LEDs

Relay

Pulse inhib active

Bit 0

none

open

(bridge X2.1-X2.2 open)

Bit 0

none

open

Mains frequency is 60Hz

Bit 2

none

open

Relay status

Bit 8

none

open

(0=relay off / 1=relay on)

Bit 8

none

open

Device switched off

Bit 9

--

closed

Wrong device

Bit 10

--

----

Bus module active

Bit 11

none

----

(0=no bus module / 1=bus module active)

 

 

 

Thyristor short-circuit

Bit 14

Test LED and Load Fault LED

----

 

 

flashing alternately slowly

 

6.4 Input and output data Thyro-A

Tab. 6 Cyclic input and output data with Thyro-A 1A...H1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Mains voltage L1

integer

2

[V]

6

Switch-on time TS

integer

2

[period]

8

Switch-on angle alpha

integer

2

[0.01 °el]

10

Total setpoint

integer

2

4096=100%

12

Fault (see table 14b)

integer

2

-

14

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Tab. 7 Cyclic input and output data with Thyro-A 1A...HRL1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load current L1

float

4

[A]

8

Mains voltage L1

integer

2

[V]

10

Switch-on time TS

integer

2

[period]

12

Switch-on angle alpha

integer

2

[0.01 °el]

14

Total setpoint

integer

2

4096=100%

16

Fault (see table 14b)

integer

2

-

18

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

16

Page 16
Image 16