24
6.6 Input and output data Thyro-Step Controller

Tab. 23 Cyclic input and output data TSC mode

6.7 Input and output data Thyro Input/Output Unit

Tab. 24 Cyclic input and output data TIO mode

Offset Input data, actual values Data type Size Unit
0 AC input 1 float 4 [A],[V]
4 AC input 2 float 4 [A],[V]
8 AC input 3 float 4 [A],[V]
12 Power float 4 [W]
16 Energy float 4 [kWh]
20 DC input 1 integer 2 4096=100%
22 DC input 2 integer 2 4096=100%
24 DC input 3 integer 2 4096=100%
26 Mains voltage integer 2 [V]
28 Period duration integer 2 [μs]
30 Temperature integer 2 [°C]
32 Fault (see table 25b) integer 2 -
34 Status (see table 25b) integer 2 -
36 Analog output 4 integer 2 4096=100%
38 Steps integer 2 -
40 Total setpoint Integer 2 4096=100%
Offset Output data, setpoint Data type Size Unit
0 Master setpoint integer 2 4096=100%
Offset Input data, actual values Data type Size Unit
0 AC input 1 float 4 [A],[V]
4 AC input 2 float 4 [A],[V]
8 AC input 3 float 4 [A],[V]
12 Power float 4 [W]
16 Energy float 4 [kWh]
20 DC input 1 integer 2 4096=100%
22 DC input 2 integer 2 4096=100%
24 DC input 3 integer 2 4096=100%
26 Mains voltage integer 2 [V]
28 Period duration integer 2 [μs]
30 Temperature integer 2 [°C]
32 Fault (see table 25b) integer 2 -
34 Status (see table 25b) integer 2 -
Offset Output data, setpoint Data type Size Unit
0 Digital output integer 2 -
2 Analog output 1 integer 2 4096=100%
4 Analog output 2 integer 2 4096=100%
6 Analog output 3 integer 2 4096=100%
8 Analog output 4 integer 2 4096=100%
10 Analog output 5 integer 2 4096=100%
12 Analog output 6 integer 2 4096=100%