6.6 Input and output data Thyro-Step Controller
Tab. 23 Cyclic input and output data TSC mode
Offset | Input data, actual values | Data type | Size | Unit |
0 | AC input 1 | float | 4 | [A],[V] |
4 | AC input 2 | float | 4 | [A],[V] |
8 | AC input 3 | float | 4 | [A],[V] |
12 | Power | float | 4 | [W] |
16 | Energy | float | 4 | [kWh] |
20 | DC input 1 | integer | 2 | 4096=100% |
22 | DC input 2 | integer | 2 | 4096=100% |
24 | DC input 3 | integer | 2 | 4096=100% |
26 | Mains voltage | integer | 2 | [V] |
28 | Period duration | integer | 2 | [μs] |
30 | Temperature | integer | 2 | [°C] |
32 | Fault (see table 25b) | integer | 2 | - |
34 | Status (see table 25b) | integer | 2 | - |
36 | Analog output 4 | integer | 2 | 4096=100% |
38 | Steps | integer | 2 | - |
40 | Total setpoint | Integer | 2 | 4096=100% |
Offset | Output data, setpoint | Data type | Size | Unit |
0 | Master setpoint | integer | 2 | 4096=100% |
6.7 Input and output data Thyro Input/Output Unit
Tab. 24 Cyclic input and output data TIO mode
Offset | Input data, actual values | Data type | Size | Unit |
0 | AC input 1 | float | 4 | [A],[V] |
4 | AC input 2 | float | 4 | [A],[V] |
8 | AC input 3 | float | 4 | [A],[V] |
12 | Power | float | 4 | [W] |
16 | Energy | float | 4 | [kWh] |
20 | DC input 1 | integer | 2 | 4096=100% |
22 | DC input 2 | integer | 2 | 4096=100% |
24 | DC input 3 | integer | 2 | 4096=100% |
26 | Mains voltage | integer | 2 | [V] |
28 | Period duration | integer | 2 | [μs] |
30 | Temperature | integer | 2 | [°C] |
32 | Fault (see table 25b) | integer | 2 | - |
34 | Status (see table 25b) | integer | 2 | - |
Offset | Output data, setpoint | Data type | Size | Unit |
0 | Digital output | integer | 2 | - |
2 | Analog output 1 | integer | 2 | 4096=100% |
4 | Analog output 2 | integer | 2 | 4096=100% |
6 | Analog output 3 | integer | 2 | 4096=100% |
8 | Analog output 4 | integer | 2 | 4096=100% |
10 | Analog output 5 | integer | 2 | 4096=100% |
12 | Analog output 6 | integer | 2 | 4096=100% |
24