Tab. 11 Cyclic input and output data with Thyro-A 2A...HRLP1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load voltage L3

float

4

[V]

8

Load current L1

float

4

[A]

12

Load current L2

float

4

[A]

16

Load current L3

float

4

[A]

20

Power L1

float

4

[W]

24

Power L3

float

4

[W]

28

Total power

float

4

[W]

32

Mains voltage L1

integer

2

[V]

34

Mains voltage L3

integer

2

[V]

36

Switch-on time TS

integer

2

[period]

38

Total setpoint

integer

2

4096=100%

40

Fault (see table 14b)

integer

2

-

42

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Tab. 12 Cyclic input and output data with Thyro-A 3A...H1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load voltage L2

float

4

[V]

8

Load voltage L3

float

4

[V]

12

Mains voltage L1

integer

2

[V]

14

Mains voltage L2

integer

2

[V]

16

Mains voltage L3

integer

2

[V]

18

Switch-on time TS

integer

2

[period]

20

Switch-on angle alpha

integer

2

[0.01 °el]

22

Total setpoint

integer

2

4096=100%

24

Fault (see table 14b)

integer

2

-

26

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%