5. Settings

5.1 Setting the protocol

The Ethernet bus module supports various real time Ethernet bus systems. The desired system can be selected using the rotary switch “Protocol”. For ProfiNet this needs to be set to 0.

5.2 Setting the number of slots

The number of devices which are connected to the Ethernet bus module is set with the rotary switch “Slots”. After switching on, the Ethernet bus module reads all the parameters of the device. Following this it starts communicating.

Attention: To change the number of slots when switched on, the switch “Slots” must first be turned to 0. Communication with the master is then interrupted. Following this the desired number can be set. After leaving the position 0 you have about 2 seconds time for this.

5.3 Setting the device name

Every IO device is identified by its device name. The setting of the device name can be undertaken using, for example, the program “Step 7 – HW Config” in the menu “Target system / Ethernet / Edit Ethernet participant…”

Fig. 1 Configuration & LED displays

1Terminal X1

2Terminal X2

3Terminal X3

4Terminal X4

5Terminal X5

6Terminal X6

7Terminal X7

8Terminal X8

9Ethernet Port

10Terminal X11

11SYS LED

12COM0 (BF) LED

13COM1 (SF) LED

14Fault LED

15Switch Slots

16Switch Protocol

12

Page 12
Image 12
AEG Thyro-S H1 manual Settings, Setting the protocol, Setting the number of slots, Setting the device name