6.9 Acyclic data transmission (parameterization)

Via the acyclic parameter data transmission, parameters of the devices can be changed or selected. Cyclical and acyclical services can be used in the network simultaneously.

Read data record “RDREC”:

For reading access to a data record, the slot, index and length of the data record must be entered. At step 7 and when using the SFB 52 the Logical Address of the slot is to be entered instead of the slot. As such the device at slot X1 is to be activated as the device at slot 1.

Error code

Meaning

DE80B000

The unit does not recognize the parameter (invalid index)

DE80B100

The length entry of the parameter is incorrect

DE80B200

The projected slot is not occupied

DE80B300

The actual unit type does not match the set unit type

Write data record “WRREC”:

For writing access to a data record, the slot, index, length of the data record and the new value must be entered. At step 7 and when using the SFB 53 the Logical Address of the slot is to be entered instead of the slot.

Error code

Meaning

DF80B000

The unit does not recognize the parameter (invalid index)

DF80B100

The length entry of the parameter is incorrect

DF80B200

The projected slot is not occupied

DF80B300

The actual unit type does not match the set unit type

DF80B600

The parameter cannot be changed

DF80B700

Invalid range of values of a parameter

You will find the parameter tables (acyclic) of each of the device types in Appendix 17 (A).