3.3 Processing the setpoint Thyro-Step Controller

Only local setpoints, no bus setpoint

Analog input at control terminal X6.1 or X6.4 (depending on X6.7) of the TSC > Do not connect anything to terminal X2.1 of the power controller.

-The bus module is fully functional. The analog signal from the control terminal X6.1 or X6.4 is used as setpoint.

Setpoint from the bus module (X22.3), no local setpoint

> Connect the ground to terminal X2.1 of the TSC.

- The master setpoint of the Ethernet bus module is used.

Bus setpoint, switching over to “local” in case of bus fault

Only use the setpoint of the bus module if there is an IO connection.

> Connect terminal X2.1 of the TSC to one of the terminals X1.1 to X8.1 of the bus module.

-If there is an IO connection the master setpoint is used. If there is no IO connection then the analog setpoint is used.

Switching over to bus / local setpoint value switchable for each controller in operation

Individual setpoint from the bus module for each power controller.

> Connect terminal X2.1 of the power controller to one of the terminals X1.5 to X8.5 of the bus module.

-The power controllers can be switched over individually (targeted) via the bus between master setpoint and the analog setpoint.

3.4Freely addressable digital outputs

>As long as the terminals X1.5 to X8.5 of the bus module are not being used for switching over the set- point, these can be used as switch outputs.

>Connect the relay to a 24 V DC coil voltage for free use. The idle circuit is integrated. The actuating current is a maximum 120 mA per output. As a result it is possible to switch over, for example, the room ventilators, anti-condensation heating, circuit breakers or control lamps via the bus.

Relais Control

10

Page 10
Image 10
AEG Thyro-S H1 manual Processing the setpoint Thyro-Step Controller, Freely addressable digital outputs, Relais Control