Tab. 13 Cyclic input and output data with Thyro-A 3A...HRL1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load voltage L2

float

4

[V]

8

Load voltage L3

float

4

[V]

12

Load current L1

float

4

[A]

16

Load current L2

float

4

[A]

20

Load current L3

float

4

[A]

24

Mains voltage L1

integer

2

[V]

26

Mains voltage L2

integer

2

[V]

28

Mains voltage L3

integer

2

[V]

30

Switch-on time TS

integer

2

[period]

32

Switch-on angle alpha

integer

2

[0.01 °el]

34

Total setpoint

integer

2

4096=100%

36

Fault (see table 14b)

integer

2

-

38

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Tab. 14 Cyclic input and output data with Thyro-A 3A...HRLP1

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load voltage L2

float

4

[V]

8

Load voltage L3

float

4

[V]

12

Load current L1

float

4

[A]

16

Load current L2

float

4

[A]

20

Load current L3

float

4

[A]

24

Power L1

float

4

[W]

28

Power L2

float

4

[W]

32

Power L3

float

4

[W]

36

Total power

float

4

[W]

40

Mains voltage L1

integer

2

[V]

42

Mains voltage L2

integer

2

[V]

44

Mains voltage L3

integer

2

[V]

46

Switch-on time TS

integer

2

[period]

48

Switch-on angle alpha

integer

2

[0.01 °el]

50

Total setpoint

integer

2

4096=100%

52

Fault (see table 14b)

integer

2

-

54

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

19

Page 19
Image 19
AEG Thyro-S H1 manual Tab Cyclic input and output data with Thyro-A 3A...HRL1