Tab. 18 Cyclic input and output data with Thyro-A 1A...C05

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage phase 1

float

4

[V]

4

Load current phase 1

float

4

[A]

8

Load current phase 2

float

4

[A]

12

Total load current

float

4

[A]

16

Power phase 1

float

4

[W]

20

Power phase 2

float

4

[W]

24

Total power

float

4

[W]

28

Mains voltage L1

integer

2

[V]

30

Switch-on angle alpha phase 1

integer

2

[0.01 °el]

32

Total setpoint

integer

2

4096=100%

34

Fault (see table 14b)

integer

2

-

36

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Tab. 19 Cyclic input and output data with Thyro-A 1A...C07

Offset

Input data, actual values

Data type

Size

Unit

0

Load voltage L1

float

4

[V]

4

Load current L1

float

4

[A]

8

Power L1

float

4

[W]

12

Mains voltage L1

integer

2

[V]

14

Load temperature

integer

2

[°C]

16

Switch-on angle alpha

integer

2

[0.01 °el]

18

Total setpoint

integer

2

4096=100%

20

Fault (see table 14b)

integer

2

-

22

Status (see table 14b)

integer

2

-

Offset

Output data, setpoint

Data type

Size

Unit

0

Master setpoint

integer

2

4096=100%

Supported operating modes TPM; TSC; TMU

With the Thyro-Power Manager, Thyro-Step Controller and Thyro-Measurement Unit the input and output data are depend on the operating mode. The following table shows which operating mode the devices support.

Tab. 20 Supported operating modes

 

TPM

 

TSC

TIO

TMU

 

automatic

manual

 

 

 

Thyro-Power Manager

X

X

X

X

X

Thyro-Step Controller

-

-

X

X

X

Thyro-Measurement Unit

-

-

-

X

X