Battery Temperature Probe

SAG582135000

System

Application Guide

Issue AE, January 31, 2007

Spec. No. 582135000

(Model LXP48F1)

Ordering Notes

1) For a replacement plug, order P/N 524653.

Home

Battery Temperature Probe

This system can be used with one or more Battery Temperature Probes. Probe must be mounted near or on the battery to sense battery temperature. Probes connect the MCA and allows it to:

Automatically increase or decrease system output voltage to maintain battery float current as battery ambient temperature decreases or increases, respectively. Battery life can be extended when an optimum charge voltage with respect to temperature is maintained.

Issue alarms if battery temperature increases above or decreases below preset adjustable limits.

Each Distribution Cabinet provides connections up to four (4) Battery Temperature Probes. Refer to SAG589200100 for probe specifications and ordering information.

Load Shed Card (Part No. 528927)

Features

Provides eight (8) relays that can be individually configured as additional alarm relays or as Low Voltage Disconnect control relays for reducing the system load (load shed). If configured for load disconnect, control of the relays can be based upon either system voltage or battery discharge elapsed time.

Provides four (4) battery midpoint monitoring inputs.

All functions are configured and controlled by the system MCA.

External mounting.

Includes one (1) 2 ft. MCA control bus cable (P/N 524410) and one (1) control bus termination plug (P/N 524653).

See Physical Size Information for Load Shed Card dimensions.

See Load Shed Card Installation and Operating Instructions (Section 5985) for complete specifications.

Restrictions

Load shed contactors are not included.

A system battery shunt is required for timed Load Shed. MCA version 3.0 or newer is required.

Maximum number of Load Shed Cards supported by MCA is four (4). Maximum combined MCA control bus cable length must not exceed 125 feet.

Ordering Notes

1)Where MCA control bus cable lengths other than the furnished 2 ft. cable are required, order per RJ-45 MCA Control Bus Cable under Cables.